SiUS372201EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
332
3.27 Indoor Blower Does Not Have Required Parameters to
Function
Applicable
Models
FXTQ-TA
Error Code
C6-02
Outline
Indoor units perform required settings for control on the fan motor, but if the minimum required
settings are not made then information indicating as such will be included among the periodic
control status information.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the parameter information shows abnormality, it will be deemed abnormal operation.
At that point, parameter settings when initializing the fan motor will be implemented from the
beginning.
Error Reset
Conditions
If the parameter information is normal, the error will be cleared.
Supposed
Causes
Locked motor rotor condition
Corrective
Actions
Check for locked rotor condition.
Replace the indoor unit PCB or motor.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...