Field Setting from Outdoor Unit
SiUS372201EA
243
Part 5 Field Settings and Test Operation
Note(s)
In high humid areas, it is recommended to keep this setting to 0 or 1.
[2-92]:
Te target temperature upper limit
Default value: 1.
Value
[2-92]
Te target temperature upper limit
0
L
1 (default)
M
2
H
If Auto Te, then use this setting to address different load profiles. If the frequent operation is at
lower system load, then use a higher setting under [2-92].