Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
234
To activate wrong wiring automatic detection, change [2-20] to 2.
To stop the wrong wiring automatic detection, push
RETURN (BS3)
. If this function was
not aborted by pushing
RETURN (BS3)
, the unit will stop its operation after 30-90
minutes. The operation time will depend on the number of connected indoor units.
If wrong wiring is detected after operation, the outdoor unit and corresponding indoor
unit display the error code
UF-01
while the other indoor units display the error code
U9
.
oH
is displayed if no wrong wiring is detected. (Press the
RETURN (BS3)
button to
finish.)
If operation stops and the outdoor unit displays
UF-18
, operation has been canceled to
prevent failure of the compressor due to wrong wiring. The indoor unit with wrong wiring
identified before the cancellation displays the error code
UF
while the other indoor units
display the error code
U9
. Check and correct the wiring and then restart operation.
This function can be used when the outdoor temperature is between –5°C and 43°C
(23°F and 109°F) and the indoor temperature is between 20°C and 27°C (68°F and
81°F).
If the indoor temperature is outside the above range, either cooling or heating is
automatically started to bring the indoor temperature to the suitable temperature.
If the outdoor temperature is outside the above range or the indoor temperature is
outside the above range even after cooling or heating, the error code
E-2
or
E-3
is
displayed, and the function cannot be used.
If
E-4
appears during operation, there may be wrong wiring between indoor units that
are largely different in capacity from each other or the additional refrigerant amount may
be insufficient. Check the wiring of indoor units and confirm that the additional
refrigerant amount has been calculated correctly.
This function can be used after test operation.
Error code during using this function and troubleshooting:
Error code
Cause
Troubleshooting
E-2
Indoor temperature is out of operating range.
Conduct cooling or heating operation to keep
the indoor temperature within the operating
range.
E-3
Outdoor temperature is out of operating
range.
This function cannot be used.
E-4
The high pressure does not rise above a
predetermined value or the low pressure does
not fall below a predetermined value.
Check the wiring of indoor units and confirm
the additional refrigerant amount.
E-5
The number of connected indoor units is one,
or an error is occurring in one of the indoor
units.
Take measures for the indoor unit in which the
abnormality is occurring.
UF-01
Detected wrong wiring after this function.
Check the wiring of indoor units where
UF
error occurring.
UF-18
Detected wrong wiring with cancelled this
function. (Due to compressor protection)
Check the wiring of indoor units where
UF
error occurring.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...