Field Setting from Outdoor Unit
SiUS372201EA
225
Part 5 Field Settings and Test Operation
[1-35]:
shows the latest prediction code.
[1-36]:
shows the 2nd last prediction code.
[1-37]:
shows the 3rd last prediction code.
[1-40]:
shows the current cooling comfort setting.
[1-41]:
shows the current heating comfort setting.
[1-42]:
shows the current high pressure sensor value (psi).
[1-43]:
shows the current low pressure sensor value (psi).
[1-44]:
shows the current compressor speed (Hz).
[1-45]:
shows the current EEV (heat exchanger upper) opening (pulse divided by 10).
[1-46]:
shows the current EEV (heat exchanger lower) opening (pulse divided by 10).
[1-47]:
shows the current compressor 1 discharge thermistor value (°F).
[1-48]:
shows the current compressor 2 discharge thermistor value (°F).
[1-49]:
shows the current compressor 1 body thermistor value (°F).
[1-50]:
shows the current outdoor air thermistor value (°F).
[1-51]:
shows the current compressor suction thermistor value (°F).
[1-52]:
shows the current subcooling gas thermistor value (°F).
[1-53]:
shows the current heat exchanger gas (upper) thermistor value (°F).
[1-54]:
shows the current heat exchanger gas (lower) thermistor value (°F).
[1-55]:
shows the current deicer right thermistor value (°F).
[1-56]:
shows the compressor run time (hour divided by 100).
[1-57]:
shows the current subcooling of (heat exchanger right) (°F).
[1-58]:
shows the current EEV (heat exchanger left) opening (pulse divided by 10).
[1-59]:
shows the current subcooling of (heat exchanger left) (°F).
[1-60]:
shows the current compressor 2 body thermistor value (°F).
[1-61]:
shows the current subcooling liquid thermistor value (°F).
[1-62]:
shows the current suction pipe thermistor value (°F).
[1-63]:
shows the current receiver inlet thermistor value (°F).
[1-64]:
shows the current heat exchanger liquid (upper) thermistor value (°F).
[1-65]:
shows the current heat exchanger liquid (lower) thermistor value (°F).
[1-66]:
shows the current heat exchanger liquid (left) thermistor value (°F).
[1-67]:
shows the current deicer (left) thermistor value (°F).
[1-68]:
shows the current heat exchanger gas (left) thermistor value (°F).
[1-69]:
shows the compressor average load.
[1-70]:
shows the current receiver gas purge thermistor value (°F).
[1-71]:
shows the current subcooling injection thermistor value (°F).
[1-72]:
shows the current electrical components box thermistor value (°F).
[1-73]:
shows the current cooling jacket outlet thermistor value (°F).
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...