Specifications
SiUS372201EA
31
Part 1 General Information
Model name
REYQ168AAYDA
REYQ192AAYDA
Power supply
3 phase, 460 V, 60 Hz
3 phase, 460 V, 60 Hz
1 Cooling
capacity
Nominal
Btu/h
(kW)
168,000 (49.2)
192,000 (56.3)
Rated
160,000 (46.9)
184,000 (53.9)
2 Heating
capacity
Nominal
Btu/h
(kW)
189,000 (55.4)
216,000 (63.3)
Rated
180,000 (52.8)
206,000 (60.4)
Casing color
Ivory white (5Y7.5/1)
Ivory white (5Y7.5/1)
Dimensions: (H × W × D)
in. (mm)
65-3/8 × 48-13/16 × 30-1/8 (1,660 × 1,240 × 765)
65-3/8 × 68-7/8 × 30-1/8 (1,660 × 1,750 × 765)
Heat exchanger
Cross fin coil
Cross fin coil
Compressor Type
Hermetically sealed scroll type
Hermetically sealed scroll type
Volume
m³/h
14.2 + 22.7
18.9 + 18.9
Number of
revolutions
r/min
6,684 + 6,684
5,586 + 5,586
Motor output
kW
4.09 + 6.96
5.82 + 5.82
Starting method
Soft start
Soft start
Fan
Type
Propeller fan
Propeller fan
Motor output ×
Number of units
kW
0.65 × 2
0.95 × 2
Airflow rate
cfm
(m³/min)
9,675 (274)
13,650 (386.5)
Drive
Direct drive
Direct drive
Connecting
pipes
Liquid pipe
in. (mm)
5/8 (15.9) C1220T (brazing connection)
5/8 (15.9) C1220T (brazing connection)
Suction gas pipe
in. (mm)
1-1/8 (28.6) C1220T (brazing connection)
1-1/8 (28.6) C1220T (brazing connection)
High/Low pressure
gas pipe
in. (mm)
7/8 (22.2) C1220T (brazing connection)
1-1/8 (28.6) C1220T (brazing connection)
Weight
lbs (kg)
802 (364)
972 (441)
Sound pressure level
(Reference data)
dB(A)
65
67
Sound power level
(Reference data)
dB
85
87
Safety devices
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Defrost method
Deicer
Deicer
Capacity control
%
2-100
4-100
Refrigerant
Refrigerant name
R-410A
R-410A
Charge
lbs (kg)
25.8 (11.7)
25.8 (11.7)
Control
Electronic expansion valve
Electronic expansion valve
Standard accessories
Installation manual, Operation manual,
Connection pipes, Clamps
Installation manual, Operation manual,
Connection pipes, Clamps
Drawing No.
4D134609A
4D134609A
Notes:
1.
2.
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...