Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
232
[2-7]:
Eco level setting for Eco mode via External control adaptor.
Eco mode can be activated by short circuit the terminal on External control adaptor
(Optional) according to [2-7] setting. ([2-64] should be “0”)
This unit can operate with “Te or Tc fix control” and “Eco mode”. Eco mode means
“VRT” control.
If the terminal on external control adapter is not connected by short circuit with [2-7] ≠ 0,
the system operates according to [2-8] or [2-9] setting.
Default value: 0
Value
[2-7]
Meaning
Level
0 (default)
Inactive
—
1
Eco mode active by low noise
terminal short-circuit
Standard
2
Eco mode activate by demand
terminal short-circuit
2-C short circuit: Low
3-C short circuit: Standard
[2-8]:
Te target temperature during cooling operation
Default value: 2
Value
[2-8]
Tc target
0
Auto (6-17°C) (42.8-62.6°F)
2 (default)
6°C (42.8°F)
3
7°C (44.6°F)
4
8°C (46.4°F)
5
9°C (48.2°F)
6
10°C (50.0°F)
7
11°C (51.8°F)
Change [2-8] to 0, 2-7 in function of required operation method during cooling.
For more information and advice about the effect of these settings, see
Energy Saving and
Optimum Operation
[2-9]:
Tc target temperature (Tc fix control)
Default value: 6
Value
[2-9]
Tc target
0
Auto (38-46°C) (100.4-114.8°F)
1
41°C (105.8°F)
3
43°C (109.4°F)
6 (default)
46°C (114.8°F)
Change [2-9] to 0, 1, 3 or 6 in function of required operation method during heating.
For more information and advice about the effect of these settings, see
Energy Saving and
Optimum Operation
[2-10]:
The heating capacity cut offset temperature setting.
Sets the difference from the set temperature at which the heating capacity is cut.
Default value: 0
Value
[2-10]
Description
0 (default)
Set tempe2.0°C (3.6°F)
1
Set tempe1.0°C (1.8°F)
2
Set tempe0.5°C (0.9°F)
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...