SiUS372201EA
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
250
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation
sound
Rated
Level 1
Level 2
Level 3
Approx. 55 dB (target)
Approx. 50 dB (target)
Approx. 45 dB (target)
Note 1: Above values are for reference only (measured in silent room)
Note 2: Above values are for 1 module only.
Operation sound level set with External low noise setting
Operation sound
during low noise
mode can be set with
External low noise
level setting (Factory
setting is level 2.)
Low noise mode instructing
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low noise
operation start setting
Time set with night-time low
noise operation end setting
Operation sound during
night-time low noise
operation mode can be set
with night-time low noise
operation level setting.
(Factory setting is OFF.)
Night-time
Operation sound level set with
night-time low noise operation
setting
6:00 AM
8:00 PM 10:00 PM 12:00 AM
7:00 AM 8:00 AM
Set with night-time low noise operation end setting.
(Factory setting is 8:00 AM.)
Set with night-time low noise operation start setting.
(Factory setting is 10:00 PM.)
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with night-time low noise
operation start setting
Low noise mode
instructing
Operation sound set with
External low noise setting
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation start setting.
(Factory setting is 10:00 PM.)
Set with night-time low noise operation end setting.
(Factory setting is 8:00 AM.)
Low noise
mode instructing
Operation sound set with
External low noise setting
Night-time
Time set with night-time low noise
operation end setting
Operation sound during
low noise mode can be
set with External quiet
operation level setting. (Factory
setting is level 2.)
Operation sound during
night-time low noise operation
mode can be set with night-time
low noise operation level
setting. (Factory setting is OFF.)
When external low noise
instruction is received during
the operation with night-time
low noise operation mode.
Level 2 precedes level 1 and
level 3 precedes level 2.
Operation sound level set
with night-time low noise
operation setting
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...