SiUS372201EA
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
226
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
COOL/HEAT
selection
Several systems as 1 zone change
over COOL/HEAT:
INDIVIDUAL:
VRV
indoor unit or
A-B-C input set mode.
MASTER: System is the
COOL/HEAT master unit.
SUB: System is not a
COOL/HEAT master.
2.
0
0
Individual
Unified Master
Unified Sub
0
1
2
2
Low noise/
demand address
Used to make address setting for
low noise/demand operation.
2.
0
2
Address:
0
~
31
3
0
1
5
Indoor fan forced
H
Used to force the fan of indoor unit
to H tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat
Used to force all indoor units to
operate forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
7
Eco level setting
for Eco mode via
External control
adaptor
Used to make setting of Eco level
for Eco mode via External control
adaptor
2.
0
7
Inactive
Eco mode active by low noise
terminal short-circuit
Eco mode active by demand
terminal short-circuit
0
1
2
8
Te setting
(Cooling
operation)
Used to make setting of targeted
evaporating temperature for
cooling operation.
2.
0
8
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C (46.4°F)
9°C (48.2°F)
10°C (50.0°F)
11°C (51.8°F)
0
2
3
4
5
6
7
9
Tc setting
Used to make setting of targeted
condensing temperature for
heating operation.
2.
0
9
Auto
41°C (105.8°F)
43°C (109.4°F)
46°C (114.8°F)
0
1
3
6
10
The heating
capacity cut
offset
temperature
setting
Used for heating capacity cut offset
temperature setting.
2.
1
0
Default 2.0°C (3.6°F)
1.0°C (1.8°F)
0.5°C (0.9°F)
0
1
2
12
External low
noise setting/
demand setting
Used to receive external low noise
or demand signal.
2.
1
2
Input LNO/DE
OFF
ON
0
1
13
AIRNET address Used to set address of AIRNET.
2.
1
3
Address:
0
~
63
6
0
3
16
Heat pump
lockout 1
Used for heat pump lockout.
2.
1
6
OFF
ON
0
1
18
High ESP setting
FAN
Fan high static pressure setting
2.
1
8
OFF
ON
0
1
19
Phased
installation
setting
Used to make setting for phased
installation.
2.
1
9
Normal installation
Single module to dual module
installation
0
1
20
Additional
refrigerant
charge/Wrong
wiring automatic
detection for
Branch Selector
Used to perform additional
refrigerant charging operation
(compressor operation) and wrong
wiring automatic detection for
Branch Selector.
2.
2
0
OFF
Refrigerant charging ON
Wrong wiring automatic
detection ON
0
1
2
21
Refrigerant
recovery and
vacuuming
Used to set the system to
refrigerant recovery mode (without
compressor run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic night-
time low noise
operation
Automatic night-time low noise
operation.
Time for the operation is subject to
the start and end time settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
0
1
2
3
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...