Capacity Range
SiUS372201EA
17
Part 1 General Information
4. Capacity Range
4.1 Connection Ratio
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Type
Min.
connection
ratio
Max. connection ratio
Types of connected
indoor units
Type of connected air
treatment equipment
When using
only
FXDQ-M,
FXSQ07TA,
FXSQ07TB,
FXMQ-PB,
FXAQ-P
When using at
least one
FXFQ07/09T,
FXZQ05TA,
FXZQ05TB,
FXSQ05TA,
FXSQ05TB
Other
indoor unit
models
FXMQ-MF
When
FXMQ-MF is
only
connected
When
FXMQ-MF
and indoor
units are
connected
Single
outdoor
units
6-14 ton
50%
200%
1
180%
1
200%
1
100%
100%
2
16-20 ton
180%
1
180%
1
Double outdoor units
160%
1
160%
1
Notes:
1.
2.
3.
If the operational capacity of indoor units is more than 130%, low airflow
operation is enforced in all the indoor units. This limitation can be deactivated
through field setting. Refer to page 239 for detail.
When outdoor-air processing units (FXMQ-MF) and standard indoor units are
connected, the total connection capacity of the outdoor-air processing units
(FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And
the connection ratio must not exceed 100%.
For indoor units used for cooling only (do not connect to Branch Selector unit
when using for heat recovery), total capacity index of cooling only indoor units
must be 50% or less than the total capacity index of the outdoor units.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...