SiUS372201EA
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
222
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
To quit and return to the initial status, press the
MODE (BS1)
button.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
Now the
SET (BS2)
button is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit’s fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
Press the
SET (BS2)
button 18 times; result segment display:
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
To change the value of the setting, press the
SET (BS2)
button until the required value appears
on the segment indication. When achieved, define the setting value by pressing the
RETURN
(BS3)
button once. To the chosen setting, confirm again by pressing the
RETURN (BS3)
button.
To leave the monitoring function, press the
MODE (BS1)
button two times, you will return to the
default situation when shipped from factory.
Result: mode 2 accessed.
Res
u
lt: mode 2 setting 18 is addressed.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...