SiUS372201EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
336
Note(s)
1. Infrared presence sensor PCB and connector
Diagnosis procedure 1
Infrared presence sensor
error (Error code
CE-01
)
Turn off the power and then reconnect.
Check infrared presence sensor output; refer to
sensor and address data No. 22-25.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared presence
sensor PCB and the
connector (
1)
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
15
by the above
verification
method.
Normal.
NO
Displays
CE-01
again or
15
for
sensor and
address data.
Replace the sensor.
Model
Infrared presence
sensor PCB
Connector
FXFQ-T
A4P
X2A (A2P)
FXZQ-TA
A5P
X110A (A6P)
FXZQ-TB
A5P
X81A (A1P)
FXUQ-P
A4P
X81A (A1P)
FXUQ-PA
A4P
X81A (A1P)
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...