Troubleshooting by Error Code
SiUS372201EA
281
Part 6 Service Diagnosis
H7 - 21
Defective fan PCB (Master): M1F
Refer to the
H7
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
H7 - 22
Defective fan PCB (Master): M2F
H7 - 23
Defective fan PCB (Sub): M1F
H7 - 24
Defective fan PCB (Sub): M2F
H9 - 01
Defective outdoor air thermistor (R1T) (Master)
Refer to the
H9
flowchart and make a diagnosis of the
relevant unit based on the Error code shown to the left.
H9 - 02
Defective outdoor air thermistor (R1T) (Sub)
J3 - 16
Defective M1C discharge pipe thermistor (R15T*): Open
(Master)
*In case of REYQ72 type, R17T
Refer to the
J3
flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the Error
code shown to the left.
J3 - 17
Defective M1C discharge pipe thermistor (R15T*): Short
(Master)
*In case of REYQ72 type, R17T
J3 - 18
Defective M2C discharge pipe thermistor (R17T): Open
(Master)
J3 - 19
Defective M2C discharge pipe thermistor (R17T): Short
(Master)
J3 - 22
Defective M1C discharge pipe thermistor (R15T*): Open
(Sub)
*In case of REYQ72 type, R17T
J3 - 23
Defective M1C discharge pipe thermistor (R15T*): Short
(Sub)
*In case of REYQ72 type, R17T
J3 - 24
Defective M2C discharge pipe thermistor (R17T): Open
(Sub)
J3 - 25
Defective M2C discharge pipe thermistor (R17T): Short
(Sub)
J3 - 38
Defective M2C compressor body thermistor (R18T): Open
(Master)
J3 - 39
Defective M2C compressor body thermistor (R18T): Short
(Master)
J3 - 42
Defective M2C compressor body thermistor (R18T): Open
(Sub)
J3 - 43
Defective M2C compressor body thermistor (R18T): Short
(Sub)
J3 - 47
Defective M1C compressor body thermistor (R16T*): Open
(Master)
*In case of REYQ72 type, R18T
J3 - 48
Defective M1C compressor body thermistor (R16T*): Short
(Master)
*In case of REYQ72 type, R18T
J3 - 49
Defective M1C compressor body thermistor (R16T*): Open
(Sub)
*In case of REYQ72 type, R18T
J3 - 50
Defective M1C compressor body thermistor (R16T*): Short
(Sub)
*In case of REYQ72 type, R18T
J3 - 56
Discharge pipe warning (Master)
J3 - 57
Discharge pipe warning (Sub)
J5 - 01
Defective compressor suction thermistor (R19T) (Master)
Refer to the
J5
flowchart and make a diagnosis of the
relevant thermistor of the relevant unit based on the Error
code shown to the left.
J5 - 03
Defective compressor suction thermistor (R19T) (Sub)
J5 - 18
Error detection of suction pipe before accumulator
thermistor (R5T) (Master)
J5 - 19
Error detection of suction pipe before accumulator
thermistor (R5T) (Sub)
Error code
Troubleshooting
Error Description
Diagnosis
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...