SiUS372201EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
288
Depending on operating condition, partial refrigerant shortage may be detected even though
correct refrigerant amount is in the system. Please refer to
Refrigerant Shortage Check
on page
16I-##
_ _ 1
6 0 9
- # #
—
Heat exchanger liquid pipe thermistor
1 failure prediction (Tf1)
■ Tf1 sensor failure
Refer to
J8
troubleshooting.
16J-##
_ _ 1
6 1 0
- # #
—
Heat exchanger liquid pipe thermistor
2 failure prediction (Tf2)
■ Tf2 sensor failure
Refer to
J8
troubleshooting.
16L-##
_ _ 1
6 1 2
- # #
—
Compressor suction thermistor failure
prediction (Ts)
■ Ts sensor failure
Refer to
J5
troubleshooting.
16M-##
_ _ 1
6 1 3
- # #
—
Accumulator inlet thermistor failure
prediction (TsA)
■ TsA sensor failure
Refer to
J5
troubleshooting.
16N-##
_ _ 1
6 1 4
- # #
—
Receiver gas purge thermistor failure
prediction (Tgi)
■ Tgi sensor failure
Refer to
J9
troubleshooting.
16O-##
_ _ 1
6 1 5
- # #
—
Liquid pipe thermistor failure
prediction (TL)
■ TL sensor failure
Refer to
J7
troubleshooting.
16P-##
_ _ 1
6 1 6
- # #
—
Heat exchanger gas pipe thermistor 1
failure prediction (Tg1)
■ Tg1 sensor failure
Refer to
J6
troubleshooting.
16Q-##
_ _ 1
6 1 7
- # #
—
Heat exchanger gas pipe thermistor 2
failure prediction (Tg2)
■ Tg2 sensor failure
Refer to
J6
troubleshooting.
16S-##
_ _ 1
6 1 9
- # #
—
Subcooling injection thermistor failure
prediction (Tm)
■ Tm sensor failure
Refer to
J7
troubleshooting.
16U-##
_ _ 1
6 2 1
- # #
—
Electrical box air outlet thermistor
failure prediction (Tjeva)
■ Tjeva sensor failure
Refer to
J9
troubleshooting.
16V-##
_ _ 1
6 2 2
- # #
—
High pressure sensor failure
prediction (HP)
■ HP sensor failure
Refer to
JA
troubleshooting.
16W-##
_ _ 1
6 2 3
- # #
—
Low pressure sensor failure
prediction (LP)
■ LP sensor failure
Refer to
JC
troubleshooting.
20A-##
_ _ 2
0 0 1
- # #
—
Heat exchanger freeze up prediction
■ Tb sensor failure
■ Freeze
Melt frost on the outdoor heat exchanger.
30A-##
_ _ 3
0 0 1
# # #
_ _ #
Indoor unit electronic expansion valve
leak (evaporator) prediction
■ Tb sensor failure
■ Indoor leakage
Th1: Refer to
C9
troubleshooting.
Th2: Refer to
C4
troubleshooting.
Th3: Refer to
C5
troubleshooting.
LP: Refer to
JC
troubleshooting.
If the above error is not seen, the corresponding
indoor electronic expansion valve and expansion
valve coil can be considered.
31A-##
_ _ 3
1 0 1
# # #
_ _ #
Indoor unit thermistor failure
prediction (Th1)
■ Th1 sensor failure
■ Th2 sensor failure
■ Th3 sensor failure
Th1: Refer to
C9
troubleshooting.
Th2: Refer to
C4
troubleshooting.
Th3: Refer to
C5
troubleshooting.
31B-##
_ _ 3
1 0 2
# # #
_ _ #
Indoor unit thermistor failure
prediction (Th2)
■ Th1 sensor failure
■ Th2 sensor failure
■ Th3 sensor failure
Th1: Refer to
C9
troubleshooting.
Th2: Refer to
C4
troubleshooting.
Th3: Refer to
C5
troubleshooting.
31C-##
_ _ 3
1 0 3
# # #
_ _ #
Indoor unit thermistor failure
prediction (Th3)
■ Th1 sensor failure
■ Th2 sensor failure
■ Th3 sensor failure
Th1: Refer to
C9
troubleshooting.
Th2: Refer to
C4
troubleshooting.
Th3: Refer to
C5
troubleshooting.
43A-##
_ _ 4
3 0 1
- 0 0
—
Refrigerant shortage and refrigerant
leakage prediction (detected during
non-operation)
■ HP sensor failure
■ Refrigerant leak or shortage
HP: Refer to
JA
troubleshooting.
If the above error is not seen, refrigerant shortage
or leakage from the system can be considered. (
)
43B-##
_ _ 4
3 0 2
- 0 0
—
Refrigerant shortage and refrigerant
leakage prediction (detected during
cooling operation)
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. (
)
43C-##
_ _ 4
3 0 3
- 0 0
—
Refrigerant shortage and refrigerant
leakage prediction (detected during
cooling and heating simultaneous
operation)
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. (
)
43D-##
_ _ 4
3 0 4
- 0 0
—
Refrigerant shortage and refrigerant
leakage prediction (detecting during
heating operation)
■ Refrigerant leak or shortage
Check for refrigerant leakage.
Check for refrigerant shortage. (
)
47A-##
_ _ 4
7 0 1
- 0 0
—
Outdoor-indoor communication failure
prediction
■ Outdoor unit control PCB
failure
■ Indoor PCB failure
■ Outdoor-indoor
communication line failure
—
Prediction code
Seven-segment display
Description
Possible cause
Tech tips
Produ
ct
type c
ode
Predic
tion
code
Predic
tion
sub co
de
AirNet
addres
s
display
flag
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...