SiUS372201EA
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
192
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote
controller is resetting when returning to the normal mode.
13 (23)
0
Setting of airflow rate
Standard
High ceiling 1
High ceiling 2
—
1
Airflow direction setting
4-direction
airflow
3-direction airflow
2-direction
airflow
—
2
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
4
Setting of airflow direction
adjustment range
Draft prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure
selection
Standard
High static
pressure
—
—
6
External static pressure
settings
Refer to page on the right for details.
14 (24)
4
Optional kit setting (UV lamp
+ humi economizer)
Refer to page on the right for details.
5
Dry mode set temperature
Room
temperature
Same as cooling
mode set
temperature
—
—
9
Mold proof operation setting
—
Standard
For high
humidity areas
—
11
Gas furnace test mode
OFF
Low heat
High heat
—
15 (25)
0
Drain pump operation setting
—
ON
OFF
—
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped
—
—
2
Setting of direct duct
connection
Not equipped
Equipped
—
—
3
Interlocked operation
between humidifier and drain
pump
Not
interlocked
Interlocked
—
—
5
Individual setting of
ventilation
Normal
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
1c
0
Room temperature display
Room
temperature is not
displayed
Room
temperature is
displayed
—
—
1
Thermistor sensor for auto
changeover and setback
control by the remote
controller
Utilize the return
air thermistor
Utilize the
remote
controller
thermistor
—
—
3
Access permission level
setting
Level 2
Level 3
—
—
1e
2
Setback availability
N/A
Heat only
Cool only
Cool/heat
14
Setting "restricted / permitted"
of airflow block
Refer to page on the right for details.
Mode
No.
(Note 2)
First
Code
No.
Setting Contents
Second Code No.
Reference
Page
01
02
03
04
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...