Troubleshooting by Error Code
Part 6 Service Diagnosis
406
3.72 Improper Combination of Indoor, Branch Selector and
Outdoor Units
Applicable
Models
All indoor unit models
Branch Selector unit
All outdoor unit models
Error Code
UA
Method of Error
Detection
A difference occurs in data by the type of refrigerant between indoor, Branch Selector and
outdoor units.
The number of indoor units is out of the allowable range.
Signal transmission between indoor, Branch Selector and outdoor units is abnormal.
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit main PCB
Mismatch of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit main PCB was not carried out after replacing to spare PCB.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...