SiUS372201EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
276
Note(s)
1. The system can keep operating, however, be sure to check and repair.
2. The system may or may not continue operation depending on the conditions.
Outdoor
Unit
H1
l
Box air thermistor abnormality
H3
l
Harness abnormality (between outdoor unit main PCB and inverter PCB)
H7
l
Outdoor fan PCB abnormality
H9
l
Outdoor air thermistor abnormality
J3
l
Discharge pipe thermistor abnormality
Compressor body thermistor abnormality
J5
l
Compressor suction thermistor abnormality
Suction pipe before accumulator thermistor abnormality
J6
l
Heat exchanger deicer thermistor abnormality
Heat exchanger gas pipe thermistor abnormality
J7
l
Receiver inlet thermistor abnormality
Subcooling heat exchanger liquid pipe thermistor abnormality
Subcooling injection thermistor abnormality
J8
l
Heat exchanger liquid pipe thermistor abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor abnormality
Receiver gas purge thermistor abnormality
Electrical box air outlet thermistor abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
Inverter PCB abnormality
L2
l
Momentary power failure during test operation
L4
l
Inverter radiation fin temperature rise abnormality
L5
l
Compressor instantaneous overcurrent
L8
l
Compressor overcurrent
L9
l
Compressor startup abnormality
LC
l
Transmission error between inverter PCB and outdoor unit main PCB
P1
l
Power supply voltage imbalance
P4 (
1)
l
Inverter radiation fin temperature abnormality
PJ
l
Field setting abnormality after replacing outdoor unit main PCB or combination of
PCB abnormality
System
U0 (
1)
k
Refrigerant shortage
U1
l
Reverse phase, Open phase, Power supply frequency issue
U2
l
Power supply insufficient or instantaneous abnormality
U3
l
Check operation not executed
U4
l
Transmission error between indoor units and outdoor units, open phase in power
supply wiring
U5
l
Transmission error between remote controller and indoor unit
U7
l
Transmission error between outdoor units
U8
l
Transmission error between main and sub remote controllers
U9
l
Transmission error between indoor units and outdoor units in the same system
UA
l
Improper combination of indoor, Branch Selector and outdoor units
Incorrect gas furnace connecting number
Incorrect electric heater capacity setting
UC (
1)
k
Address duplication of centralized controller
UE
l
Transmission error between centralized controller and indoor unit
UF
l
System not set yet
UH
l
System abnormality, refrigerant system address undefined
Climate Talk communication system combination error (before initial setting for
communication completes)
Climate Talk communication system combination error (after initial setting for
communication completes)
Error
code
Operation
lamp
Error contents
Reference
page
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...