SiUS372201EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
372
3.54 Momentary Power Failure during Test Operation
Applicable
Models
All outdoor unit models
Error Code
L2
Method of Error
Detection
Momentary power failure is detected by the PCB.
Error Decision
Conditions
Judgment is made by AC power frequency detection circuit on the outdoor unit main PCB.
Supposed
Causes
Defective wiring
Defective outdoor unit main PCB
Troubleshooting
Error
recurs after
turning OFF the power
and ON again.
Any
disconnection
of connectors, loose
contact or wiring
disconnection in the
transmission wirings to the
outdoor unit main
PCB?
NO
YES
YES
NO
Temporary problem
Correct any fault.
Replace the outdoor unit
main PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...