Outline of Control (Indoor Unit)
Part 4 Functions and Control
160
prevention operation will be conducted. If the evaporator inlet temperature is kept at not less than
7°C (44.6°F) for a consecutive period of 10 min., the freeze-up prevention operation will be reset.
6. Thermostat status
7. The following models have the drain pump as standard equipment.
FXFQ-T, FXZQ-TA, FXZQ-TB, FXUQ-P, FXUQ-PA, FXEQ-P, FXDQ-M, FXSQ-TA, FXSQ-TB,
FXMQ-PB, FXMQ-TB
8. Program dry display
No set temperature and airflow rate of the remote controller are displayed.
9. Thermostat status
Set temperature when operating the program dry mechanism.
10. Fan operation
By setting the remote controller to Fan, the fan will operate with thermostat OFF in set temperature
control operation mode.
11. Set wind direction
According to wind direction instruction from the remote controller, the wind direction is set to 100%
horizontal while in heating operation.
12. Fan
According to fan speed instruction from the remote controller, the fan is put into operation in LL
mode while in heating operation.
13. Wind direction
When the heating thermostat turns OFF, the wind direction will be set to 100% horizontal.
14. Hot start
After the start of heating operation or the end of defrost operation, the hot start control will terminate
if the temperature at the condenser outlet (indoor heat exchanger liquid pipe temperature) exceeds
34°C (93.2°F), or if Tc is above 52°C (125.6°F), or if 3 minutes have elapsed.
15. Thermostat status
16. Outlet air temperature drop protection
When the set temperature is below 24°C (75.2°F) or the electronic expansion valve opening is
small, the protection will be activated.
17. Hu indicates the Humidifier connected to the wiring modification adaptor.
It is not related to the Humidifier terminals on the PCB of FXTQ-TA or CXTQ-TA.
18. Only for CXTQ-TA.
Refer to
Gas Furnace Control (CXTQ-TA Models)
OFF
ON
a
b
Set temperature
a = b = 1°C (1.8°F) or 0.5°C (0.9°F)
The values a and b depend on the field setting 12(22)-2.
Suction air temperature
b
a
–2°C (28.4°F)
–4°C (24.8°F)
Suction air temp.
Set temp.
b
a
(3)
(2)
(1)
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...