EM11 User’s Manual
Appendix II
155
Code
Parameter Name
Setting range
Default
Property
b6-01
AO1 output function
selection
6: Motor rotational speed corresponding to
0~Max. operation frequency
7: Output current corresponding to 0~1000A
8: Output voltage corresponding to 0~1000V
9: Output torque corresponding to
(-200%~200%) motor rated torque
10: Pulse input corresponding to
0Hz~100kHz
11: AI1 corresponding to 0~10V
12: AI2 corresponding to 0~10V
13: AI3 corresponding to 0~10V
14: Length corresponding to 0~Length
setting value
15: Count value corresponding to 0~Count
setting value
16: Communication setting corresponding to
0~32767
0
☆
b6-02
AO2 output function
selection
1
☆
b6-03
Maximum FMP output
frequency
0.01 kHz ~50.00 kHz
50.00 kHz
☆
b6-04
AO1 offset coefficient -100.0% ~100.0%
0.0%
☆
b6-05 AO1
gain
-10.00~10.00
1.00
☆
b6-06
AO2 offset coefficient -100.0% ~100.0%
0.00%
☆
b6-07 AO2
gain
-10.00
~10.00
1.00
☆
Group b7 : Virtual DI (VDI)/Virtual DO (VDO)
b7-00 VDI1
function
selection 0~49
0
★
b7-01 VDI2
function
selection 0~49
0
★
b7-02 VDI3
function
selection 0~49
0
★
b7-03 VDI4
function
selection 0~49
0
★
b7-04 VDI5
function
selection 0~49
0
★
b7-05
VDI state setting mode
Unit's digit: VDI1.
0: Valid decided by state of VDOx
1: Valid decided by b7-06
Ten's digit: VDI2.
0, 1 (same as VDI1)
Hundred's digit: VDI3.
0, 1 (same as VDI1)
Thousand's digit: VDI4.
0, 1 (same as VDI1)
Ten thousand's digit: VDI5.
0, 1 (same as VDI1)
00000
☆
Appendix II
EM11 User’s Manual
156
Code
Parameter Name
Setting range
Default
Property
b7-06
VDI state setting
Unit's digit: VDI1.
0: Invalid
1: Valid
Ten's digit: VDI2
0, 1 (same as VDI1)
Hundred's digit: VDI3
0, 1 (same as VDI1)
Thousand's digit: VDI4
0, 1 (same as VDI1)
Ten thousand's digit: VDI5.
0, 1 (same as VDI1)
00000
☆
b7-07
Function selection for
AI1 used as DI
0~49 0
★
b7-08
Function selection for
AI2 used as DI
0~49 0
★
b7-09
Function selection for
AI3 used as DI
0~49 0
★
b7-10
Valid state selection for
AI used as DI
Unit's digit: AI1.
0: High level valid
1: Low level valid
Ten's digit: AI2.
0, 1 (same as unit's digit)
Hundred's digit: AI3.
0, 1 (same as unit's digit)
0
☆
b7-11
VDO1 function
selection
0: connect with physical DIx internally
1~38
38
☆
b7-12
VDO2 function
selection
0: connect with physical DIx internally
1~38
38
☆
b7-13
VDO3 function
selection
0: connect with physical Dix internally
1~38
38
☆
b7-14
VDO4 function
selection
0:connect with physical Dix internally
1~38
38
☆
b7-15
VDO5 function
selection
0: connect with physical Dix internally
1~38
38
☆
b7-16
VDO1 output delay 0.0s~3000.0s
0.0s
☆
b7-17
VDO2 output delay 0.0s~3000.0s
0.0s
☆
b7-18
VDO3 output delay 0.0s~3000.0s
0.0s
☆
b7-19
VDO4 output delay 0.0s~3000.0s
0.0s
☆
b7-20
VDO5 output delay 0.0s~3000.0s
0.0s
☆