EM11 User’s Manual
2. Product Information
17
Model
Recommend
power of
braking resistor
Recommend
resistance value of
braking resistor
Braking
unit
Remarks
EM11- G2-075
16k W
≥
1.2
Ω
External
Three-phase 380V
EM11- G3-d75/P3-1d5
150W
≥
300
Ω
Built-in as
standard
No special
instructions
EM11- G3-1d5/P3-2d2
150W
≥
220
Ω
EM11- G3-2d2/P3-004
250W
≥
200
Ω
EM11- G3-004/P3-5d5
300W
≥
130
Ω
EM11- G3-5d5/P3-7d5
400W
≥
90
Ω
EM11- G3-7d5/P3-011
500W
≥
65
Ω
EM11- G3-011/P3-015
800W
≥
43
Ω
EM11- G3-015/P3-018
1000W
≥
32
Ω
EM11- G3-018/P3-022
1300W
≥
25
Ω
Built-in as
option
Add ”-B” to the
model
EM11- G3-022/P3-030
1500W
≥
22
Ω
EM11- G3-030/P3-037
2500W
≥
16
Ω
EM11- G3-037/P3-045
3.7 kW
≥
16.0
Ω
EM11- G3-045/P3-055
4.5 kW
≥
16
Ω
Built-in as
option
Add ”-B” to the
model
EM11- G3-055/P3-075
5.5 kW
≥
8
Ω
EM11- G3-075/P3-090
7.5 kW
≥
8
Ω
EM11- G3-090/P3-110
4.5 kW×2
≥
8
Ω
×2
External EM-BU3
EM11- G3-110/P3-132
5.5 kW×2
≥
8
Ω
×2
EM11- G3-132/P3-160
6.5 kW×2
≥
8
Ω
×2
External EM-BU3H
EM11- G3-160/P3-200
16kW
≥
2.5
Ω
EM11- G3-200/P3-220
20 kW
≥
2.5
Ω
External EM-BU4H
EM11- G3-220/P3-250
22 kW
≥
2.5
Ω
EM11- G3-250/P3-280
12.5 kW×2
≥
2.5
Ω
×2
External EM-BU5H
EM11- G3-280/P3-315
14 kW×2
≥
2.5
Ω
×2
EM11- G3-315/P3-355
16 kW×2
≥
2.5
Ω
×2
EM11- G3-355/P3-400
17 kW×2
≥
2.5
Ω
×2
External EM-BU4H*2
EM11- G3-400/P3-450
14 kW×3
≥
2.5
Ω
×3
2.9.3 Braking resistor connection description
The braking resistor connection of EM11 series frequency inverter is showed as below:
Diagram 2-7 Braking resistor connection scheme
3. Installation of Frequency Inverter
EM11 User’s Manual
18
3. Installation of Frequency Inverter
3.1 Installation environment
1.
The place with indoor vents or ventilation devices.
2.
The environment temperature shall be -10
℃
~40
℃
. If the temperature is over 40
℃
but less than 50
℃
,
better to take down the cover of frequency inverter or open the front door of cabinet to facilitate heat
dissipation.
3.
Try to avoid high temperature and wet place; the humidity shall be less than 90% without frost deposit.
4.
Avoid direct sunlight.
5.
Keep away from flammable, explosive and corrosive gas and liquid.
6.
No dust, floating fiber and metal particles.
7.
Install on the place without strongly vibration. And the vibration should be not over 0.6G, Especially pay
attention to far away from the punching machine, etc.
8.
Keep away from electromagnetic interference source.
3.2 Installation direction and space
In order to not affect the service life of frequency inverter and reduce its performance, note for its
installation direction and space and correctly fasten it.
Diagram3-1 Ventilating duct installation dimension diagram of frequency inverter
Power class
Installation dimension
A
B
≤
7.5kW
≥
20mm
≥
100mm
11kW - 30kW
≥
50mm
≥
200mm
≥
37kW
≥
50mm
≥
300mm
Please install the frequency inverter vertically, to send out the heat upward, and pay attention to direction of
frequency inverter to avoid inversion.
If there are several units of frequency inverter installed, please install them side by side, do not to install up
and down.