Code
Parameter Name
Setting range
Default
Property
for V/F separation
d2-14
Voltage rise time of V/F
separation
0.0s~1000.0s
Note: It indicates the time for the voltage
rising from 0 V ~ rated motor voltage.
0.0s
☆
Group d3: Motor 2 Parameters
d3-00
Rated motor power 0.1kw~1000.0 kW
Model
dependent
★
d3-01
Rated motor voltage 1V~2000 V
Model
dependent
★
d3-02 Rated
motor
current
0.01A~655.35 A (Frequency inverter power
≤
55 kW)
0.1A~6553.5 A (Frequency inverter power
≥
75 kW)
Model
dependent
★
d3-03
Rated motor frequency 0.01 Hz~ maximum frequency
50.00Hz
★
d3-04
Rated motor rotational
speed
1rpm~65535rpm
Model
dependent
★
d3-05
Stator resistance
(asynchronous motor)
0.001
Ω
~65.535
Ω
(Frequency inverter
power
≤
55 kW)
0.0001
Ω
~6.5535
Ω
(Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-06
Rotor resistance
(asynchronous motor)
0.001
Ω
~65.535
Ω
(Frequency inverter
power
≤
55 kW)
0.0001
Ω
~6.5535
Ω
(Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-07
Leakage inductive
reactance (asynchronous
motor)
0.01mH~655.35 mH (Frequency inverter
power
≤
55 kW)
0.001mH~65.535 mH (Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-08
Mutual inductive
reactance (asynchronous
motor)
0.1mH~6553.5 mH (Frequency inverter
power
≤
55 kW)
0.01mH~655.35 mH (Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-09
No-load current
(asynchronous motor)
0.01 A ~ d3-02 (Frequency inverter power
≤
55 kW)
0.1 A ~ d3-02 (Frequency inverter power
≥
75 kW)
Model
dependent
★
d3-15
Stator resistance
(synchronous motor)
0.001
Ω
~65.535
Ω
(Frequency inverter
power
≤
55 kW)
0.0001
Ω
~6.5535
Ω
(Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-16
Shaft D inductance
(synchronous motor)
0.01mH~655.35 mH (Frequency inverter
power
≤
55 kW)
0.001mH~65.535 mH (Frequency inverter
power
≥
75 kW)
Model
dependent
★
d3-17
Shaft Q inductance
(synchronous motor)
0.01mH~655.35 mH (Frequency inverter
power
≤
55 kW)
0.001mH~65.535 mH (Frequency inverter
Model
dependent
★
Appendix II
EM11 User’s Manual
174
Code
Parameter Name
Setting range
Default
Property
power
≥
75 kW)
d3-18
Back EMF
(synchronous motor)
0.1V~6553.5 V
Model
dependent
★
d3-19
Encoder pulses per
revolution
1~32767 1024
★
d3-20 Encoder
type
0: ABZ incremental encoder
1: Resolver
2: UVW incremental encoder
3: Reversed
4: Wire-saving UVW encoder
0
★
d3-21
A, B phase sequence of
ABZ incremental
encoder
0: Forward
1: Reserve
0
★
d3-22
Encoder installation
angle
0.0°~ 359.9°
0.0°
★
d3-23
U, V, W phase sequence
of UVW encoder
0: Forward
1: Reverse
0
★
d3-24
UVW encoder angle
offset
0.0°~ 359.9°
0.0°
★
d3-28
Number of pole pairs of
resolver
1~99 1
★
d3-29
Encoder wire-break
fault detection time
0.0s: No action
0.1s~10.0s
0.0s
★
d3-30
Motor 2 auto-tuning
selection
0: No auto-tuning
1: Asynchronous motor static auto-tuning
2: Asynchronous motor complete
auto-tuning
11: Synchronous motor with-load
auto-tuning
12: Synchronous motor no-load auto-tuning
0
★
Group d4: Motor 2 Vector Control Parameters
d4-00
Speed/Torque control
selection
0: Speed control
1: Torque control mode
0
★
d4-01
Speed loop proportional
gain 1(Kp1)
0.01~10.00 0.30
☆
d4-02
Speed loop integral time
1(Ti1)
0.01s~10.00s 0.50s
☆
d4-03 Switchover frequency 1 0.00Hz ~ d4-06
5.00 Hz
☆
d4-04
Speed loop proportional
gain 2(Kp2)
0.01~10.00 0.20
☆
d4-05
Speed loop integral time
2(Ti2)
0.01s~10.00s 1.00s
☆
d4-06 Switchover frequency 2 d4-03 ~ maximum output frequency
10.00 Hz
☆
d4-07
Speed loop integral
property
0: Integral separated disabled
1: Integral separated enabled
0
☆
d4-08 ASR input filtering time 0.000s~0.100s
0.000s
☆
d4-09 ASR
output
filtering
0.000s~0.100s
0.000s
☆