EM11 User’s Manual
Appendix II
147
Code
Parameter Name
Setting range
Default
Property
b2-13
Frequency switchover
point between
acceleration time 1 and
acceleration time 2
0.00 Hz ~ maximum frequency
0.00 Hz
☆
b2-14
Frequency switchover
point between
deceleration time 1 and
deceleration time 2
0.00 ~ maximum frequency
0.00 Hz
☆
b2-15 Reverse
running
0: Enabled
1: Disabled
0
☆
b2-16
Forward/Reverse
rotation dead-zone time
0.0~3000.0s 0.0s
☆
b2-17
Running mode when set
frequency lower than
frequency lower limit
0: Run at frequency lower limit
1: Stop
2: Run at zero speed
0
☆
b2-18
Droop control
0.00Hz~10.00 Hz
0.00 Hz
☆
b2-19
Terminal JOG priority
0: Disabled
1: Enabled
0
☆
b2-20
Setting power-on time
reach threshold
0~65000 h
0 h
☆
b2-21
Setting running time
reach threshold
0~65000 h
0 h
☆
b2-22
Action after running
time reached
0: Continue to run
1: Stop
0
☆
b2-23
Cooling fan control
0: Fan working during running
1: Fan working during power on
0
☆
b2-24
Dormant frequency 0.00Hz ~wakeup frequency (b2-26)
0.00 Hz
☆
b2-25
Dormant delay time 0.0s~6000.0s
0.0s
☆
b2-26 Wakeup
frequency
Dormant frequency (b2-24)~ maximum
frequency (b0-13)
0.00 Hz
☆
b2-27 Wakeup
delay
time
0.0s~6000.0s
0.0s
☆
b2-28 Timing
function
0: Disabled
1: Enabled
0
☆
b2-29 Timing
duration
source
0: b2-30
1: AI1
2: AI2
3: AI3
(100% of analog input corresponds
to the value of b2-30)
0
☆
b2-30
Timing duration
0.0min~6500.0 min
0.0 min
☆
b2-31
This time running time
reached threshold
0.0min~6500.0 min
0.0 min
☆
b2-32 Startup
protection
0: No
1: Yes
0
☆
Group b3: Switch Input Terminal Parameters
Appendix II
EM11 User’s Manual
148
Code
Parameter Name
Setting range
Default
Property
b3-00 DI1
function
selection
0: No function
1: Forward RUN (FWD) or running
command
2: Reverse RUN (REV) or FWD/REV
running direction
3: Three-line control
4: Forward JOG (FJOG)
5: Reverse JOG (RJOG)
6: Multi-function terminal 1
7: Multi-function terminal 2
8: Multi-function terminal 3
9: Multi-function terminal 4
10: Terminal UP
11: Terminal DOWN
12: clear to zero of UP and DOWN setting
(terminal, keypad)
13: Terminal 1 for acceleration/ deceleration
time selection
14: Terminal 2 for acceleration/ deceleration
time selection
15: Frequency source switchover
16: Switchover between main frequency
source X and preset frequency
17: Switchover between auxiliary frequency
source Y and preset frequency
18:Terminal 1 for Command source
switchover
19: Terminal 2 for Command source
switchover
20: Speed control/Torque control switchover
21: Torque control prohibited
22: PID pause
23: PID integral pause
24: Reverse PID action direction
25: PID parameter switchover
26: PLC status reset
27: Swing pause
28: Counter input
29: Counter reset
30: Length count input
31: Length reset
32: Pulse input (enabled only for HDI)
33: Frequency modification enable
34:Acceleration/Deceleration prohibited
35: Motor selection terminal 1
36: Motor selection terminal 2(reserve)
37: Fault reset
1
★
b3-01 DI2
function
selection
4
★
b3-02 DI3
function
selection
9
★
b3-03 DI4
function
selection
12
★
b3-04 DI5
function
selection
13
★
b3-05
DI6/HDI function
selection
32
★
b3-06
DI7 function
selection(extend)
0
★
b3-07
DI8 function
selection(extend)
0
★