90
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
Condition for entering defrost mode
The unit starts defrosting when the following condition occurs:
• Outside temperature < Bypass damper maximum opening threshold (default = 5°C);
• Exhaust temperature < Exhaust temperature threshold
End defrost conditions
The unit ends the defrosting procedure if one of these conditions occurs:
• Exhaust temperature > Exhaust temperature threshold, or
• The “Maximum defrost duration” time has elapsed from when defrost mode starts.
Note:
when the outside temperature is very low, and the minimum time has elapsed between successive defrosts, defrosting
starts again.
OFF
ON
Byp_Damp_Max_Op_thr
Ext_T_thr
Rec_exch_def
t
t
t
Ext_T
Ext_T
T_ON
T_OFF
T_ON
30220980_207_R01
Key
Exh_T
Exhaust temperature
Ext_T
Outside temperature
Byp_ Damp_
Max_ Op_thr
Start defrost threshold
Exh_T_thr
End defrost threshold
Rec_exch_def
Heat recovery unit defrost
T_ON
Maximum defrost duration
T_OFF
Minimum time between defrosts
t
time
Fig. 9.ay
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
M
PR
E
SSOR
Ua09
Evaporator defrost start threshold
-1.0
-10.0
5.0
°C
R/W HR1526
AV3027
Evaporator defrost end threshold
50.0
DfrStart-
Thrsh
99.9
°C
R/W HR1527
AV3028
Ua12
Defrost delta bypass damper
3.0
0.0
10.0
K
R/W HR1528
AV3029
Evaporator defrost start delay time
5
0
65535
min
R/W HR1529
PIV3030
Ua15
Enable refrigerant ciruit for active heat recovery unit
-
0
1
-
R
DI705
BV1163
Defrost time for stop compressor
5
0
65535
min
R/W HR1530
PIV3031
Ua18
Defrost minimum time
1
0
65535
min
R/W HR1531
PIV3032
Defrost maximum time
5
0
65535
min
R/W HR1532
PIV3033
Time between two defrost
30
0
65535
min
R/W HR1533
PIV3034
Ua21
Defrost dripping time
90
0
9999
s
R/W HR1534
PIV3035
Post-dripping time [s]
30
0
9999
s
R/W HR1535
PIV3036
Ua24
BLDC minimum speed in defrost
40.0
-999.9
999.9
-
R/W HR1536
AV3037
Reverse valve delta P
3.0
0.0
5.0
bar
R/W HR1537
AV3038
Ua27
Defrost: delay time before change over
20
0
900
s
R/W HR1538
PIV3039
Defrost: delay time after change over
10
0
900
s
R/W HR1539
PIV3040
Ua30
Fans request during evaporator defrost
3
0
3
%
R/W HR1540
PIV3041
Fans request during evaporator defrost
30.0
0.0
100.0
%
R/W HR1541
AV3042
Fans request during evaporator defrost
0
0
100
%
R/W HR1542
PIV3043
Fans request during evaporator defrost: dripping
2
0
3
%
R/W HR1543
PIV3044
Fans request during evaporator defrost: dripping
30.0
0.0
100.0
%
R/W HR1544
AV3045
Fans request during evaporator defrost: dripping
100
0
100
%
R/W HR1545
PIV3046
Fans request during evaporator defrost: post dripping
2
0
3
%
R/W HR1546
PIV3047
Fans request during evaporator defrost: post dripping
30.0
0.0
100.0
%
R/W HR1547
AV3048
Fans request during evaporator defrost: post dripping
100
0
100
%
R/W HR1548
PIV3049
Ua33
Disable Low supply temperature alarm
TRUE
0
1
-
R/W CS250
BV250
Tab. 9.bf