125
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
M
PR
E
SSOR
Ub16
BLDC envelope confi guration - Discharge gas temperature control
threshold for Zone 1a (SIAM scroll only)
105.0
70.0
350.0
°C
R/W HR1875
AV3357
BLDC envelope confi guration - Discharge gas limit temperature for
Zone 1a (SIAM Scroll only)
110.0
80.0
350.0
°C
R/W HR1876
AV3358
Ub17
BLDC informations - Envelope Type: Siam compressor
-
0
1
-
R
DI768
BV1226
BLDC envelope confi guration - Discharge gas temperature control
threshold (SIAM scroll only: for zone 1b)
115.0
70.0
350.0
°C
R/W HR1877
AV3359
BLDC envelope confi guration - Discharge gas limit temperature (SIAM
Scroll only: for Zone 1b)
120.0
80.0
350.0
°C
R/W HR1878
AV3360
Ub18
BLDC envelope confi guration - Action distance from High Temperatu-
re limit (to reduce speed rate)
20.0
10.0
999.9
°C
R/W HR1879
AV3361
BLDC envelope confi guration - Pause between speed reductions
when discharge temp. is over control limit
90
1
300
s
R/W HR1880
IV3362
BLDC envelope confi guration - Speed Reduction percentage when
discharge temp is over control limit
3.0
0.5
60.0
-
R/W HR1881
AV3363
Ub19
Custom minimum evaporating temperature
-25.0
-999.9
999.9
°C
R/W HR1882
AV3364
Custom maximum temperature condensing
70.0
-999.9
999.9
°C
R/W HR1883
AV3365
Ub20
BLDC envelope confi guration - Regol. Evd SubType: 0=null; 1=SSH;
2=DSH; 3= DLT
1
1
3
-
R/W HR1884
IV3366
BLDC envelope confi guration - Time constant of discharge temp sensor 50.0
1.0
800.0
-
R/W HR1885
AV3367
Ub21
BLDC envelope confi guration - SetPoint of Discharge SH (sent to EVD) 35.0
10.0
45.0
K
R/W HR1886
AV3368
BLDC envelope confi guration - Setpoint off set for Discharge Super
Heat regulation activation
2.0
0.0
99.9
K
R/W HR1887
AV3369
BLDC envelope confi guration - Hysteresys for Discharge Super Heat
regulation deactivation
2.0
0.0
99.9
K
R/W HR1888
AV3370
Ub22
BLDC envelope confi guration - SetPoint of Discharge Temp (sent to EVD) 105.0
75.0
110.0
°C
R/W HR1889
AV3371
BLDC envelope confi guration - Setpoint off set for Discharge Limit
Temp. regulation activation
8.0
0.0
99.9
°C
R/W HR1890
AV3372
BLDC envelope confi guration - Hysteresys for Discharge Limit Temp.
regulation deactivation
5.0
0.0
99.9
°C
R/W HR1891
AV3373
Ub23
Automatically generated - Maximum semiautomatic alarm reset retry
number
3
0
5
-
R/W HR1892
IV3374
Automatically generated - Time threshold for semiautomatic reset
60
1
1440
min
R/W HR1894
PIV3375
Ub24
Automatically generated - Reset type: 0= Manual - 1= Semiautomatic FALSE
0
1
-
R/W CS459
BV458
Ub25
BLDC informations - Debug: FB version x
-
0
9
-
R
IR613
PIV3927
BLDC informations - Debug: FB version y
-
0
9
-
R
IR614
PIV3928
BLDC informations - Debug: FB version z
-
0
999
-
R
IR615
PIV3929
BLDC informations - Debug: FB version beta
-
0
9
-
R
IR616
PIV3930
Uc01
Automatically generated - 0: Stop; 1: Run; 2: Alarm; 3: Crankcase
heating; 4:DCbus ready)
-
0
9
-
R
IR571
PIV3885
Inverter Power Plus Info - Drive temperature
-
-999.9
999.9
°C
R
IR572
AV3886
Automatically generated - see doc
-
0
99
-
R
IR573
PIV3887
Uc02
Inverter Power Plus Info - Speed reference [Hz/rps]
-
-999.9
999.9
-
R
IR574
AV3888
Inverter Power Plus Info - Current rotor speed [Hz]
-
-9999.9
9999.9
-
R
IR575
AV3889
Inverter Power Plus Info - Current rotorspeed [rpm]
-
0
65535
-
R
IR576
PIV3890
Uc03
Inverter Power Plus Info - Current motor current [A]
-
0.0
9999.9
-
R
IR577
AV3891
Inverter Power Plus Info - Current motor voltage [V]
-
0
65535
-
R
IR578
PIV3892
Inverter Power Plus Info - Current motor consumption [W]
-
-9999.99
9999.99
-
R
IR579
AV3893
Uc04
Automatically generated - DC bus voltage
-
0
999
-
R
IR580
PIV3894
Automatically generated - DC bus ripple
-
0
999
-
R
IR581
PIV3895
Uc05
Automatically generated - PWM switching frequency (0: 4kHz,
1: 6kHz, 2: 8kHz)
-
0
4
-
R
IR582
PIV3896
Automatically generated - Pre-ramp output frequency reference
-
-999.9
999.9
-
R
IR583
AV3897
Uc06
Inverter Power Plus Info - Status register bit 15
-
0
1
-
R
DI726
BV1184
Inverter Power Plus Info - Status register bit 14
-
0
1
-
R
DI727
BV1185
Inverter Power Plus Info - Status register bit 13
-
0
1
-
R
DI728
BV1186
Inverter Power Plus Info - Status register bit 12
-
0
1
-
R
DI729
BV1187
Inverter Power Plus Info - Drive in alarm
-
0
1
-
R
DI730
BV1188
Inverter Power Plus Info - Status register bit 10
-
0
1
-
R
DI731
BV1189
Inverter Power Plus Info - Power supply status: 0=OK; 1=loss of a
power supply phase (L1)
-
0
1
-
R
DI732
BV1190
Inverter Power Plus Info - Motor overload
-
0
1
-
R
DI733
BV1191
Inverter Power Plus Info - Autotune running
-
0
1
-
R
DI734
BV1192
Inverter Power Plus Info - Status register bit 06
-
0
1
-
R
DI735
BV1193
Inverter Power Plus Info - Switching frequency derating ON
-
0
1
-
R
DI736
BV1194
Inverter Power Plus Info - Fan ON
-
0
1
-
R
DI737
BV1195
Inverter Power Plus Info - Under voltage
-
0
1
-
R
DI738
BV1196
Inverter Power Plus Info - Motor PTC overheating
-
0
1
-
R
DI739
BV1197
Inverter Power Plus Info - Relay confi g. ON
-
0
1
-
R
DI740
BV1198
Inverter Power Plus Info - Safety input status (STO); 0=drive enable; 1=
drive disable
-
0
1
-
R
DI741
BV1199
Inverter Power Plus Info - Speed register bit 15
-
0
1
-
R
DI742
BV1200