Qa 01 0: Off ; 1: Startup; 2: On; 3: Shutdown;
-
0
9
-
R
IR20 2
PIV3 592
Fresh air damper
-
0
1
-
R
DI38 4
BV84 2
Fresh air damper
-
-999.0
999.0
-
R
IR15 5
AV35 47
Mixing damper - Hardware value writes from board
-
0
1
-
R
DI39 1
BV84 9
Mixing damper
-
-999.0
999.0
-
R
IR15 3
AV35 45
Exhaust air damper - Hardware value writes from board
-
0
1
-
R
DI38 7
BV84 5
Exhaust air damper
-
-999.0
999.0
-
R
IR16 9
AV35 61
Qa 03 Heating exchanger type
0
0
4
-
R
HR1 293 PIV2 801
Heating exchanger type
0
0
4
-
R
HR1 293 PIV2 801
Bypass damper
-
-999.0
999.0
-
R
IR15 1
AV35 43
Thermal wheel
-
-999.0
999.0
-
R
IR16 5
AV35 57
Bypass damper - Hardware value writes from board
-
0
1
-
R
DI37
BV82
Enable post heating coil
-
0
1
-
R
DI65 4
BV11 12
Qa 12 Discharge pressure
-
-999.9
999.9
bar
R
IR09 8
AV34 90
Condensing temperature
-
-999.9
999.9
°C
R
IR22 4
AV36 14
Discharge temperature
-
-999.9
999.9
°C
R
IR10 1
AV34 93
IR22 5
IV36 15
OnOff compressor countdown
-
0
999
s
R
IR22 6
IV36 16
Compressor request
-
0.0
100.0
%
R
IR22 8
AV36 17
Suction temperature
-
-999.9
999.9
°C
R
IR10 7
AV34 99
Compressor - Hardware value writes from board
-
0
1
-
R
DI42 7
BV88 5
Suction pressure
-
-999.9
999.9
bar
R
IR10 4
AV34 96
EVD parameters - Status variables - Evaporation temperature
-
-999.9
999.9
°C
R
IR22 9
AV36 18
Qa 15 Discharge pressure
-
-999.9
999.9
bar
R
IR09 8
AV34 90
EVD parameters - Status variables - Condensing temperature
-
-999.9
999.9
°C
R
IR23 0
AV36 19
Discharge temperature
-
-999.9
999.9
°C
R
IR10 1
AV34 93
For mask usage
-
0
99
-
R
IR23 1
IV36 20
For mask usage
-
0
999
-
R
IR23 2
IV36 21
BLDC power request
-
0.0
100.0
%
R
IR23 4
AV36 22
Suction temperature
-
-999.9
999.9
°C
R
IR10 7
AV34 99
BLDC Compressore run request scaled with the custom max. limit -
-999.0
999.0
-
R
IR23 5
AV36 23
Suction pressure
-
-999.9
999.9
bar
R
IR10 4
AV34 96
EVD parameters - Status variables - Evaporation temperature
-
-999.9
999.9
°C
R
IR22 9
AV36 18
Qa 18 0=Null;1=OK;2=Max.comp.rat;3=Max.dsc.P.;4=Curr.limit;5=Max.
suct.P.;6=Min.comp.rat;7=Min.Del taP;8=Min.dsc.P.;9=Min.suct.P.
-
0
9
-
R
IR23 6
IV36 24
BLDC to EVD parameters - EVD regulation subtype
-
0
9
-
R
IR23 7
IV36 25
For mask usage
-
0
99
-
R
IR23 8
IV36 26
BLDC Compressore run request scaled with the custom max. limit -
-999.0
999.0
-
R
IR23 5
AV36 23
EVD parameters - Status variables - Superheat
-
-999.0
999.0
K
R
IR23 9
AV36 27
EVD parameters - Status variables - Superheat
-
-9.9
9.9
K
R
IR23 9
AV36 27
Inverter Power Plus Info - Current rotor speed [rps]
-
-999.0
999.0
-
R
IR24 0
AV36 28
EVD parameters - Status variables - Valve opening
-
-999.0
999.0
%
R
IR24 1
AV36 29
Out of envelop countdown
IR24 2
IV36 30
Suction pressure
-
-999.9
999.9
bar
R
IR10 4
AV34 96
Discharge pressure
-
-999.9
999.9
bar
R
IR09 8
AV34 90
Qa 21 EVD parameters - Status variables - Valve position
-
0
999
-
R
IR24 3
IV36 31
EVD parameters - Status variables - Valve opening
-
-999.0
999.0
%
R
IR24 1
AV36 29
For mask usage
-
-999.9
999.9
-
R
IR24 4
AV36 32
BLDC to EVD parameters - EVD regulation subtype
-
0
9
-
R
IR23 7
IV36 25
EVD parameters - Status variables - Superheat
-
-99.9
99.9
K
R
IR23 9
AV36 27
EVD parameters - Status variables - Discharge superheat
-
-99.9
99.9
K
R
IR24 5
AV36 33
Discharge temperature
-
-999.9
999.9
°C
R
IR10 1
AV34 93
Qa 24 Humidifi cation/Dehumidifi cation: Control probe (See Defi ned_
Word: HUMDEHUM_CTRLPRB_ XX)
0
0
2
-
R
HR1 318 PIV2 826
Humidifi cation/Dehumidifi cation: Relative humidity variable
-
-999.9
999.9
-
R
IR24 6
AV36 34
Humidifi cation/Dehumidifi cation: Absolute humidity variable
-
-999.9
999.9
-
R
IR24 7
AV36 35
Humidifi cation/Dehumidifi cation: Absolute humidity control
-
0
1
-
R
DI65 5
BV11 13
Current humidity set point - Setpoint
-
LowLi mVal HiLi mVal %rh
R
HR9 81
AV25 03
Humidifi cation/Dehumidifi cation: Absolute setpoint
-
-999.9
999.9
-
R
IR24 8
AV36 36
Humidifi cation/Dehumidifi cation: Absolute humidity control
-
0
1
-
R
DI65 5
BV11 13
Humidifi cation request from PID Seq
-
-999.9
999.9
%
R
IR24 9
AV36 37
Dehumidifi cation request
-
-999.9
999.9
%
R
IR25 0
AV36 38