133
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
I
NFOR
M
A
TI
ONS
Qa 27 Fresh air temperature - Analog input confi gured
-
0
1
-
R
DI02 8
BV48 6
Fresh air temperature
-
-999.9
999.9
°C
R
IR06 2
AV34 54
Saturation temperature - Analog input confi gured
-
0
1
-
R
DI04 8
BV50 6
Saturation temperature
-
-999.9
999.9
°C
R
IR07 7
AV34 69
Dew point set point for dehumidifi cation
-
-999.9
999.9
°C
R
IR25 1
AV36 39
Dehumidifi cation request
-
-999.9
999.9
%
R
IR25 0
AV36 38
Qa 30 Auxiliary Regulation 1 - Input selection
0
0
13
-
R
HR1 584 PIV3 079
Auxiliary regulation 1: Informations - Regulation value
-
-999.9
999.9
-
R
IR25 2
AV36 40
Auxiliary Regulation 1 - Regulation setpoint
20.0
- 9999.9
9999.9
-
R
HR9 80
AV25 02
Auxiliary output 1
-
-999.0
999.0
-
R
IR17 1
AV35 63
Auxiliary output 1
-
0
1
-
R
DI46 0
BV91 8
Qa 33 Auxiliary Regulation 1 - Input selection
0
0
13
-
R
HR1 584 PIV3 079
Auxiliary regulation 2: Informations - Regulation value
-
-999.9
999.9
-
R
IR25 3
AV36 41
Auxiliary Regulation 2 - Regulation setpoint
20.0
- 9999.9
9999.9
-
R
HR1 602 AV30 97
Auxiliary output 2
-
-999.0
999.0
-
R
IR17 3
AV35 65
Auxiliary output 2
-
0
1
-
R
DI46 4
BV92 2
Qa 36 Auxiliary Regulation 1 - Input selection
0
0
13
-
R
HR1 584 PIV3 079
Auxiliary regulation 3: Informations - Regulation value
-
-999.9
999.9
-
R
IR25 4
AV36 42
Auxiliary Regulation 3 - Regulation setpoint
20.0
- 9999.9
9999.9
-
R
HR1 616 AV31 11
Auxiliary output 3
-
-999.0
999.0
-
R
IR17 5
AV35 67
Auxiliary output 3
-
0
1
-
R
DI46 8
BV92 6
Qa 39 Auxiliary Regulation 1 - Input selection
0
0
13
-
R
HR1 584 PIV3 079
Auxiliary regulation 4: Informations - Regulation value
-
-999.9
999.9
-
R
IR25 5
AV36 43
Auxiliary Regulation 4 - Regulation setpoint
20.0
- 9999.9
9999.9
-
R
HR1 630 AV31 25
Auxiliary output 4
-
-999.0
999.0
-
R
IR17 7
AV35 69
Auxiliary output 4
-
0
1
-
R
DI47 2
BV93 0
Qa 42 Scheduler is active
-
0
1
-
R
DI65 6
BV11 14
Scheduler source (DIN, Party mode, SPV, cpCO, thTune)
-
0
9
-
R
IR25 6
PIV3 644
Scheduler is active
-
0
1
-
R
DI65 6
BV11 14
Unit status currently active: 0=Off ; 1=Economy;
2=Pre-comfort; 3=Comfort
-
0
9
-
R
IR25 7
PIV3 645
Qa 45 KWater modbus variables - Cooling/Heating mode
-
0
1
-
R
DI66 0
BV11 18
KWater modbus variables - External temperature
-
-999.9
999.9
-
R
IR25 8
AV36 46
KWater modbus variables - KAir circuit temperature
-
-999.9
999.9
-
R
IR25 9
AV36 47
Unit status kwater
-
0
99
-
R
IR26 0
PIV3 648
Qa 48 Power request
-
0.0
100.0
%
R
IR26 1
AV36 49
Actual production of rack (kg/h-lb/h)
-
0.0
100.0
-
R
IR26 2
AV36 50
Pump running hour humifog
-
0
999999
h
R
IR26 3
PIV3 651
Machine status
-
0
99
-
R
IR26 5
IV36 52
Qa 51 IEC: request
-
0.0
100.0
%
R
IR26 6
AV36 53
Actual production of rack (kg/h-lb/h)
-
0.0
100.0
-
R
IR26 7
AV36 54
Pump running hour humifog
-
0
999999
-
R
IR26 8
PIV3 655
Machine status
-
0
99
-
R
IR27 0
IV36 56
Qa 54 Split an int value into digits - Compressor 1 circuit 1 active
-
0
1
-
R
DI66 1
BV11 19
Split an int value into digits - Compressor 2 circuit 1 active
-
0
1
-
R
DI66 2
BV11 20
Split an int value into digits - rps bldc circ1 rotor speed coming
from inverter
-
-999.9
999.9
-
R
IR27 1
AV36 57
Split an int value into digits - Opn1 - EEV position of circ.1
-
0
999
-
R
IR27 2
IV36 58
Split an int value into digits - dSP1-Discharge press. probe of circ.1 -
-99.9
99.9
-
R
IR27 3
AV36 59
Split an int value into digits - Show the Compressor info circuit 1
on user interface
-
0
1
-
R
DI66 3
BV11 21
Split an int value into digits - ScP1-Suction press. of circ.1
-
-99.9
99.9
-
R
IR27 4
AV36 60
Split an int value into digits - Show the Compressor info circuit 1
on user interface
-
0
1
-
R
DI66 3
BV11 21
Unitstatus (0=Off ByDI;1=Off ByKeyb;2=Off BySched;3=Of-
fByBMS;4=Off ByChgOvr;5=Off ByAl;6=Dfr;7=StdBy;14
=FCOn;15=CoolOn;16=HeatOn;20=Offl
ine)
-
0
99
-
R
IR27 5
IV36 61
Compressor request
-
0.0
100.0
%
R
IR22 8
AV36 17
Qa 57 Split an int value into digits - Compressor 1 circuit 2 active
-
0
1
-
R
DI66 4
BV11 22
Split an int value into digits - Compressor 2 circuit 2 active
-
0
1
-
R
DI66 5
BV11 23
Split an int value into digits - rps bldc circ2 rotor speed coming
from inverter
-
-999.9
999.9
-
R
IR27 6
AV36 62
Split an int value into digits - Opn1 - EEV position of circ.1
-
0
999
-
R
IR27 2
IV36 58
Split an int value into digits - dSP1-Discharge press. probe of circ.1 -
-99.9
99.9
-
R
IR27 3
AV36 59
Split an int value into digits - Show the Compressor info circuit 2
on user interface
-
0
1
-
R
DI66 6
BV11 24
Split an int value into digits - ScP1-Suction press. of circ.1
-
-99.9
99.9
-
R
IR27 4
AV36 60
Split an int value into digits - Show the Compressor info circuit 2
on user interface
-
0
1
-
R
DI66 6
BV11 24
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......