185
Software update
k.air +030220981 rel. 1.2 - 01.12.2020
13. SOFTWARE UPDATE
The k.Air controller application program can be updated as follows:
• Update from computer via USB cable connection;
• Update via USB pen drive;
• Update with fi le transfer via FTP;
Note:
to update the controller, the .ap1 application update fi le is required, supplied by CAREL INDUSTRIES S.p.A.
Important:
only application software supplied and approved by CAREL INDUSTRIES S.p.A. can be loaded onto the k.Air con-
troller.
Important:
before updating the k.Air controller via USB connection, check in the system menu that the USB Host port is
enabled (path Settings > USB Settings > Pen drive).
• Use only FAT formatted pen drives.
• On k.Air Large models, do not use the controller’s two USB ports at the same time.
• Do not use mass storage devices with a current draw higher than 500 mA.
Important:
when updating the application software, any confi gurations previously set by the user will be lost. Consequently,
before starting the update, the confi guration can be saved and then reloaded after updating the application software. For details
on the procedure for saving and loading the user confi gurations, see the chapter “Commissioning”.
13.1 Update via U
SB
cable
On k.Air models equipped with a USB device (Slave) port, the application program can be updated by connecting a computer
to the controller via USB cable:
1. Connect the computer and the c.pCO controller via USB cable using the USB device port
30220980_043_R01
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
ID
5
ID
6
ID
7
ID
8
IDC1
J3
J4
J5
J14
J13
J12
J15
d
r
a
c
S
M
B
4 3 2 1
J25 BMS2
Tx/Rx GND
Tx/Rx GND
J26 FBus2
J21
NO14
C14
NC14
NO15
C15
NC15
ID15H
ID15
USB connector from computer
Fig. 13.a
1. The controller will be seen by the system as an external drive; save the .ap1 fi le to the folder called “UPGRADE”;
2. Unplug the cable; the k.Air controller operating system will automatically update the application software. The update procedu-
re will last a few minutes, then the unit will reboot.
3. Return to the system menu and run the Application > Wipe retain command, or alternatively go to screen Ac30 and run the
“Clear permanent memory” command.