Hardware installation
k.air +030220981 rel. 1.2 - 01.12.2020
Connection of analogue outputs
Example connection diagrams:
30220980_026_R01
Vout
24Vac/28...36 Vdc
0 V
Vout
Fig. 3.r
30220980_027_R01
G
G0
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
ID
5
ID
6
ID
7
ID
8
IDC1
J1
J2
J3
J4
J5
d
r
a
c
S
M
B
d
r
a
c
s
u
B
d
l
e
i
F
+V
te
rm
GND
+5VREF
J24
U6
U7
U8
GND
J6
ID
9
ID10
ID11
ID12
IDC9
J7
ID13H
ID13
IDC13
ID14
ID14H
J8
J20
J19
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
ID17
ID18
IDC17
U9
GND
U10
GND
24 Vac/28...36 Vdc
0 V
Vout
Vout
Vout
Vout
Vout
Vout
Fig. 3.s
Note :
the max output current is 10 mA.
3.6.4
D
igital outputs
Electromechanical relay digital outputs
The controller provides digital outputs with electromechanical relays; for easier assembly, the common terminals for some relays
have been grouped together. Some relays are equipped with changeover contacts. Also see the technical specifi cations table
in 0300057EN.
Maximum number of digital outputs that can be connected
D
igital inputs
k.
A
ir mini
k.
A
ir large
c.p
CO
e
NO/NC output relay
max tot 6
1
max tot 18
5
max tot 6
1
NO output relay
5
13
5
Tab. 3.p
The following tables apply in relation to the type of insulation.
Insulation type on k.Air mini andc.pCOe
Between relays in group 1 (R1, R2) and 2 (R3, R4, R5)
basic
Between relays in group 3 (R6) and relays in group 1 and 2
reinforced
Tab. 3.q
Note:
• there is basic insulation between groups 1 and 2, and therefore these must have the same voltage (generally 24 Vac or
110/230 Vac);
• between relays in groups 1 and 2 and in group 3 there is reinforced insulation, therefore group 3 can have a diff erent voltage.
Insulation type on k.Air large
Between relays in the same group
basic
Between groups of relays
reinforced
Between relays and the rest of the controller
reinforced
Tab. 3.r
Note:
• within a group, the relays have functional insulation and therefore must have the same voltage (generally 24 Vac or 110/230 Vac);
• between groups of relays there is reinforced insulation, therefore the groups can have diff erent voltages.
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......