137
Supervisor variable table
k.air +030220981 rel. 1.2 - 01.12.2020
Variable
D
escription
D
im Modbus
BAC
net
Scheduler_Cfg.SDays[7].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS053
BV53
Scheduler_Cfg.SDays[8].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS054
BV54
Scheduler_Cfg.SDays[9].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS055
BV55
Scheduler_Cfg.SDays[10].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS056
BV56
Scheduler_Cfg.SDays[11].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS057
BV57
Scheduler_Cfg.SDays[12].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS058
BV58
Scheduler_Cfg.SDays[13].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS059
BV59
Scheduler_Cfg.SDays[14].Enabled
Scheduler: confi guration - Special day - Enabled
1
CS060
BV60
Scheduler_Cfg.Vac[0].Enabled
Scheduler: confi guration - Vacation period - Enabled
1
CS061
BV61
Scheduler_Cfg.Vac[1].Enabled
Scheduler: confi guration - Vacation period - Enabled
1
CS062
BV62
Scheduler_Cfg.Vac[2].Enabled
Scheduler: confi guration - Vacation period - Enabled
1
CS063
BV63
SupplyAirFlwSw.LogicDin_RW
Supply air fl ow switch - Logic digital input
1
CS065
BV65
RetAirFlwSw.LogicDin_RW
Return air fl ow switch - Logic digital input
1
CS066
BV66
AirFlwSw.LogicDin_RW
Air fl ow switch - Logic digital input
1
CS067
BV67
AFreezeSw.LogicDin_RW
Antifreeze switch - Logic digital input
1
CS068
BV68
RemOnOff .LogicDin_RW
Remote On/Off - Logic digital input
1
CS069
BV69
SupplyFanOvld_1.LogicDin_RW
Supply fan overload 1 - Logic digital input
1
CS070
BV70
RetFanOvld_1.LogicDin_RW
Return fan overload 1 - Logic digital input
1
CS071
BV71
SupplyFanOvld_2.LogicDin_RW
Supply fan overload 2 - Logic digital input
1
CS072
BV72
RetFanOvld_2.LogicDin_RW
Return fan overload 2 - Logic digital input
1
CS073
BV73
SupplyFanInvAlrm.LogicDin_RW
Supply inverter alarm - Logic digital input
1
CS074
BV74
RetFanInvAlrm.LogicDin_RW
Return inverter alarm - Logic digital input
1
CS075
BV75
FansOvld.LogicDin_RW
Fans overload - Logic digital input
1
CS076
BV76
CompOvld.LogicDin_RW
Compressor overload - Logic digital input
1
CS077
BV77
HiPSw.LogicDin_RW
High discharge pressure switch - Logic digital input
1
CS078
BV78
LowPSw.LogicDin_RW
Low suction pressure switch - Logic digital input
1
CS079
BV79
RecoveryOvld.LogicDin_RW
Thermal wheel overload - Logic digital input
1
CS080
BV80
SrsAlrm.LogicDin_RW
Serious alarm - Logic digital input
1
CS081
BV81
GenAlrm.LogicDin_RW
Generic alarm - Logic digital input
1
CS082
BV82
GenWarning.LogicDin_RW
Generic warning - Logic digital input
1
CS083
BV83
FiltAlrm.LogicDin_RW
Filters alarm - Logic digital input
1
CS084
BV84
SupplyFiltAlrm_1.LogicDin_RW
Supply fi lter alarm 1 - Logic digital input
1
CS085
BV85
SupplyFiltAlrm_2.LogicDin_RW
Supply fi lter alarm 2 - Logic digital input
1
CS086
BV86
RetFiltAlrm.LogicDin_RW
Return fi lter alarm - Logic digital input
1
CS087
BV87
HumAlrm.LogicDin_RW
Humidifi er alarm - Logic digital input
1
CS088
BV88
MainCoilPmp1_Ovld.LogicDin_RW
Main coil pump 1 overload - Logic digital input
1
CS089
BV89
MainCoilPmp2_Ovld.LogicDin_RW
Main coil pump 2 overload - Logic digital input
1
CS090
BV90
ReHeatCoilPmp1_Ovld.LogicDin_RW
ReHeat coil pump 1 overload - Logic digital input
1
CS091
BV91
ReHeatCoilPmp2_Ovld.LogicDin_RW
ReHeat coil pump 2 overload - Logic digital input
1
CS092
BV92
PreHeatCoilPmp1_Ovld.LogicDin_RW
PreHeat coil pump 1 overload - Logic digital input
1
CS093
BV93
PreHeatCoilPmp2_Ovld.LogicDin_RW
PreHeat coil pump 2 overload - Logic digital input
1
CS094
BV94
FreshAirPreHeatCoilPmp1_Ovld.LogicDin_RW
Fresh air preHeat coil pump 1 overload - Logic digital input
1
CS095
BV95
FreshAirPreHeatCoilPmp2_Ovld.LogicDin_RW
Fresh air preHeat coil pump 2 overload - Logic digital input
1
CS096
BV96
FreshAirDampSw.LogicDin_RW
Fresh air damper switch - Logic digital input
1
CS097
BV97
SupplyDamperSw.LogicDin_RW
Supply damper switch - Logic digital input
1
CS098
BV98
RetDampSw.LogicDin_RW
Return damper switch - Logic digital input
1
CS099
BV99
MainCoilFlwSw.LogicDin_RW
Main coil fl ow switch - Logic digital input
1
CS100
BV100
PreHeatCoilFlwSw.LogicDin_RW
Pre-heating coil fl ow switch - Logic digital input
1
CS101
BV101
ReHeatCoilFlwSw.LogicDin_RW
Post-Heating coil fl ow switch - Logic digital input
1
CS102
BV102
FreshAirPreHeatCoilFlwSw.LogicDin_RW
Fresh Air Pre-Heaing coil fl ow switch - Logic digital input
1
CS103
BV103
RecoveryClogged.LogicDin_RW
Recovery clogged - Logic digital input
1
CS104
BV104
ReHeatAlrm.LogicDin_RW
Re-heating alarm - Logic digital input
1
CS105
BV105
PreHeatAlrm.LogicDin_RW
Pre-heating alarm - Logic digital input
1
CS106
BV106
MainHeatCoilAlrm.LogicDin_RW
Main coil alarm - Logic digital input
1
CS107
BV107
FreshAirPreHeatAlrm.LogicDin_RW
Fresh Air Pre-Heat alarm - Logic digital input
1
CS108
BV108
DoorSw.LogicDin_RW
Door Switch - Logic digital input
1
CS109
BV109
FireSmokeAlrm.LogicDin_RW
Fire/Smoke alarm - Logic digital input
1
CS110
BV110
FiremanOverrideSw.LogicDin_RW
Fireman override switch - Logic digital input
1
CS111
BV111
CoolHeatModeByDin.LogicDin_RW
CoolHeatModeByDin - Logic digital input
1
CS112
BV112
Din_SetP.LogicDin_RW
Setpoint by digital input - Logic digital input
1
CS113
BV113
Eco_Mode.LogicDin_RW
Eco mode - Logic digital input
1
CS114
BV114
PreComf_Mode.LogicDin_RW
Precomfort mode - Logic digital input
1
CS115
BV115
Comf_Mode.LogicDin_RW
Comfort mode - Logic digital input
1
CS116
BV116