100
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
I
D
D
escription
A
vailability
A
ction
Expiry
(months)
9.1
Air ducts. Check accessible duct section for damage
Check and repair
12
9.2
Air ducts. Check two or three representative locations on
inner duct surface for contamination, corrosion, and water
precipitation
Check and clean, not only
the visible part
12
11.1
Silencers. Check silencers for contamination, damage, and
corrosion
Check, clean and repair
12
12.1
Fan. Check for contamination, damage, and corrosion
Check, clean and repair,
check condensate drain
6
13.1
Heat exchanger. Visual inspection of air- to- air plate or
cross- fl ow heat exchanger for contamination, damage and
corrosion
Cross-fl ow or two-coil heat
recovery unit
Check, clean and repair
6
13.2
Heat exchanger. Visual inspection of air- to- air rotary
heat exchanger for contamination, damage and corrosion
Thermal wheel
Check, clean and repair
6
13.4
Heat exchanger heaters: Check for contamination damage,
corrosion and tightness
Heat recovery defrost heater
Check, clean and repair
6
13.5
Heat exchanger coolers: Check tube bundles, mist col-
lectors and condensate tray for contamination, corrosion,
damage and tightness
IEC
Check, clean and repair
3
13.6
Heat exchanger. Functional check of drain and trap
Heat recovery unit
Check, clean and repair
3
Tab. 9.bj
The characteristics of each single counter can be customised on screens Ja02 to Ja42, after setting the type as “CUSTOM” on
Ja02. To restore the default values, reset the type to “VDI 6022”.
Maintenance program
timings: VDI 6022
0.0 Hygienic insp.
Thrsh: 24m Typ:
1.1 OutAir inlets
Thrsh: 12m Typ:
VDI 6022-1
Jb02
30220980_134_R01
Following confi guration of the counters, the scheduled maintenance function is operational. Progress of the counters can be
viewed at any time in the Jb-VDI status menu.
When the counter expires, the signal will be shown on the alarm menu, and the unit may shut down (if the shutdown alarm
indicated by the closed padlock has been selected in the confi guration). Simply go to the Jb- VDI Status menu to reset the
counter and reset the signal. It is recommended to evaluate whether there are other checks that are nearing expiry, and carry
them out before resetting.
Maintenance countdown
0.0 Hygienic insp.
Remain: 17312h Res:
1.1 OutAir inlets
Remain: 7947h Res:
VDI 6022-1
Jb01
30220980_133_R01
Note:
The dirty fi lter scheduled maintenance warning, confi gurable on Ae09, is disabled if VDI management is activated. This is becau-
se it is redundant with the checks required under VDI 6022.
The pGDE only shows the title of the counter, refer to the ID present on the screen and in the table shown here in the manual.
Important:
the VDI 6022-1 function is provided to assist in managing the unit in accordance with the requirements of the
standard, as described above. The user is however always responsible for correct functioning of the equipment.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
V
D
I
Ja01
VDI Inactivity startup activation delay
48
0
65535
h
R/W HR1686
PIV3181
VDI Inactivity startup duration
5
0
65535
min
R/W HR1687
PIV3182
VDI high saturation humidity threshold
80.0
0.0
99.0
%rh
R/W HR1688
AV3183
VDI high saturation humidity diff erential
2.0
0.0
99.0
%rh
R/W HR1689
AV3184
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......