108
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa57
Unit setpoints - Return static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1143
AV2653
Unit setpoints - Return static pressure - Economy - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1143
AV2653
Unit setpoints - Return static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1144
AV2654
Unit setpoints - Return static pressure - Economy - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1144
AV2654
Unit setpoints - Return static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1145
AV2655
Unit setpoints - Return static pressure - Economy - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1145
AV2655
Aa60
Unit setpoints - Return static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1146
AV2656
Unit setpoints - Return static pressure - Pre-comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1146
AV2656
Unit setpoints - Return static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1147
AV2657
Unit setpoints - Return static pressure - Pre-comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1147
AV2657
Unit setpoints - Return static pressure - Pre-comfort - High limit value 600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1148
AV2658
Unit setpoints - Return static pressure - Pre-comfort - High limit value 600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1148
AV2658
Aa63
Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1149
AV2659
Unit setpoints - Return static pressure - Comfort - Setpoint
400.0
LowLimVal
HiLimVal
Pa
R/W HR1149
AV2659
Unit setpoints - Return static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1150
AV2660
Unit setpoints - Return static pressure - Comfort - Low limit value
200.0
MinVal_RW HiLimVal
Pa
R/W HR1150
AV2660
Unit setpoints - Return static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1151
AV2661
Unit setpoints - Return static pressure - Comfort - High limit value
600.0
LowLimVal
MaxVal_ RW Pa
R/W HR1151
AV2661
Aa66
Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1152
PIV2662
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1153
PIV2663
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1154
PIV2664
Aa69
Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1155
PIV2665
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1156
PIV2666
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1157
PIV2667
Aa72
Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Return air fl ow - Setpoint
5000
LowLimVal
HiLimVal
m^3/h
R/W HR1158
PIV2668
Unit setpoints - Return air fl ow - Low limit value
3000
0
HiLimVal
m^3/h
R/W HR1159
PIV2669
Unit setpoints - Return air fl ow - High limit value
7000
LowLimVal
65535
m^3/h
R/W HR1160
PIV2670
Aa75
Unit setpoints - Humidity - Cooling - Economy - Setpoint
60.0
LowLimVal
HiLimVal
%rh
R/W HR1161
AV2671
Unit setpoints - Humidity - Heating - Economy - Setpoint
40.0
LowLimVal
HiLimVal
%rh
R/W HR1162
AV2672
Unit setpoints - Humidity - Cooling - Economy - Low limit value
50.0
0.0
HiLimVal
%rh
R/W HR1163
AV2673
Unit setpoints - Humidity - Heating - Economy - Low limit value
35.0
0.0
HiLimVal
%rh
R/W HR1164
AV2674
Unit setpoints - Humidity - Cooling - Economy - High limit value
65.0
LowLimVal
100.0
%rh
R/W HR1165
AV2675
Unit setpoints - Humidity - Heating - Economy - High limit value
45.0
LowLimVal
100.0
%rh
R/W HR1166
AV2676
Aa78
Unit setpoints - Humidity - Cooling - Pre-comfort - Setpoint
55.0
LowLimVal
HiLimVal
%rh
R/W HR1167
AV2677
Unit setpoints - Humidity - Heating - Pre-comfort - Setpoint
45.0
LowLimVal
HiLimVal
%rh
R/W HR1168
AV2678
Unit setpoints - Humidity - Cooling - Pre-comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1169
AV2679
Unit setpoints - Humidity - Heating - Pre-comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1170
AV2680
Unit setpoints - Humidity - Cooling - Pre-comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1171
AV2681
Unit setpoints - Humidity - Heating - Pre-comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1172
AV2682
Aa81
Scheduler: confi guration - Enabled
FALSE
0
1
-
R
CS064
BV64
Unit setpoints - Humidity - Cooling - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1173
AV2683
Unit setpoints - Humidity - Heating - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1174
AV2684
Unit setpoints - Humidity - Cooling - Comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1175
AV2685
Unit setpoints - Humidity - Heating - Comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1176
AV2686
Unit setpoints - Humidity - Cooling - Comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1177
AV2687
Unit setpoints - Humidity - Heating - Comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1178
AV2688
Aa84
Enable setpoint compensation by external temperature
FALSE
0
1
-
R/W CS195
BV195
Aa87
Cooling: external temperature compensation threshold
25.0
-50.0
90.0
°C
R/W HR1179
AV2689
Cooling: external temperature compensation delta
7.0
-30.0
30.0
°C
R/W HR1180
AV2690
Cooling: maximum compensation off set
2.0
-20.0
10.0
°C
R/W HR1181
AV2691
Aa90
Heating: external temperature compensation threshold
0.0
-50.0
90.0
°C
R/W HR1182
AV2692
Heating: external temperature compensation delta
-8.0
-30.0
30.0
°C
R/W HR1183
AV2693
Heating: maximum compensation off set
-2.0
-20.0
10.0
°C
R/W HR1184
AV2694
Ab01
Actual hour
-
0
99
-
R
IR306
PIV3687
Actual minute
-
0
99
-
R
IR307
PIV3688
Day of week
-
0
9
d
R
IR383
PIV3760
Actual day
-
0
99
d
R
IR358
PIV3739
Actual month
-
0
99
month
R
IR359
PIV3740
Actual year
-
0
99
y
R
IR360
PIV3741
Scheduler: confi guration - Enabled
FALSE
0
1
-
R/W CS064
BV64
Ab06
Enable event 1
-
0
1
-
R/W CS196
BV196
Start hours event 1
-
0
23
-
R/W HR1187
PIV2696
Start minutes event 1
-
0
59
-
R/W HR1188
PIV2697
0=OFF; 1=Economy; 2=Comfort
-
0
3
-
R/W HR1189
PIV2698
Enable event 2
-
0
1
-
R/W CS197
BV197
Start hours event 2
-
0
23
-
R/W HR1190
PIV2699