Hardware installation
k.air +030220981 rel. 1.2 - 01.12.2020
Important:
• the two 230 Vac or 24 Vac/Vdc inputs on terminals J8 (ID13, ID14) or J19 (ID15, ID16) have the same common pole and
therefore both must have the same voltage (230 Vac or 24 Vac/Vdc). The insulation between the two inputs is functional; there
is reinforced insulation between the inputs and the rest of the controller;
• ID1-ID8, ID9-ID12, ID17, ID18 have functional insulation from the rest of the controller;
• for inputs with direct current voltage (24 Vdc), either the + or - can be connected to the common terminal;
Connection of digital inputs
There are no specifi c constraints on the maximum number of inputs that can be connected. For the k.Air mini controller, see the
fi gure above, while for k.Air large, a possible connection example is shown below. See 0300057EN.
30220980_025_R01
G
G0
U1
U2
U3
GND
+VDC
U4
GND
U5
GND
VG
VG0
Y1
Y2
Y3
Y4
ID
1
ID
2
ID
3
ID
4
ID
5
ID
6
ID
7
ID
8
IDC1
J1
J2
J3
J4
J5
d
r
a
c
S
M
B
d
r
a
c
s
u
B
d
l
e
i
F
+V
te
rm
GND
+5VREF
J24
U6
U7
U8
GND
J6
ID
9
ID10
ID11
ID12
IDC9
J7
ID13H
ID13
IDC13
ID14
ID14H
J8
J20
J19
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
ID17
ID18
IDC17
U9
GND
U10
GND
G
G0
24 Vac
Fig. 3.q
3.6.3
A
nalogue outputs
The controller provides non-optically isolated 0- 10 Vdc analogue outputs powered directly by the controller (k.Air mini), and
optically isolated outputs powered externally (k.Air large). See 0300057EN.
Maximum number of analogue outputs that can be connected
D
igital inputs
k.
A
ir mini
k.
A
ir large
c.p
CO
e
0-10 Vdc, optically isolated on Y1, Y2, Y3, Y4, Y5, Y6
0
6
0
0-10 Vdc, optically isolated on Y1, Y2
2
14
0
Tab. 3.n
Characteristics of analogue outputs Y...
Power supply
k.Air mini internal; k.Air large external, 24 Vac (+ 10/-15%) or 28-36 Vdc (+ 10/-20%)
on VG (+), VG0 (-) (class 2)
Precision
k.Air mini ± 3% full scale; k.Air large ± 2% full scale
Resolution
8 bit
Stabilisation time
From 1 s (slew rate 10 V/s) to 20 s (slew rate 0.5 V/s) selectable via SW
Maximum load
1 kΩ (10 mA)
Maximum connection cable length
k.Air mini 10 m; k.Air large 30 m
Tab. 3.o
Important:
• for lengths > 10 m, a shielded cable is required, with the shield connected to earth;
• other outputs of the same type can be connected in parallel to a 0-10 Vdc analogue output or an external voltage. The re-
sulting voltage will be the higher value. Correct operation is not guaranteed if actuators with voltage inputs are connected;
• for k.Air large, power analogue outputs VG-VG0 at the same voltage supplied at G-G0: connect G to VG and G0 to VG0. This
applies to both AC and DC power supplies.
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......