Alarms and signals
k.air +030220981 rel. 1.2 - 01.12.2020
C
ode
D
escription
R
eset
Eff ect
Modbus
AL232
VDI alarm - Check silencers for contamination. Damage, and
corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1235
AL233
VDI alarm - Check for contamination, damage, and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1236
AL234
VDI alarm - Visual inspection of air-to-air plate or cross-fl ow heat
exchanger for contamination damage and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1237
AL235
VDI alarm - Visual inspection of air-to-air rotary heat exchanger
for contamination, damage and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1238
AL236
VDI alarm - Heaters: Check for contamination damage, corrosion
and tightness
Automatic
Unit shutdown / Display only (parameter)
DI1239
AL237
VDI alarm - Coolers: Check tube bundles, mist collectors and
condensate tray for contamination, corrosion, damage and
tightness
Automatic
Unit shutdown / Display only (parameter)
DI1240
AL238
VDI alarm - Functional check of drain and trap
Automatic
Unit shutdown / Display only (parameter)
DI1241
AL239
VDI alarm - Supply humidity probe is needed
Automatic
Unit shutdown / Display only (parameter)
DI1242
AL240
Alarm - Door open
Automatic
Immediate unit shutdown
DI1243
AL241
Alarm - Fire/Smoke
Automatic
Immediate unit shutdown
DI1244
AL242
Serious alarm from digital input
Automatic
Immediate unit shutdown
DI1245
AL243
Generic warning from digital input
Automatic
Display only
DI1246
AL244
Supply - Dirty fi lter alarm
Automatic
Display only
DI1247
AL245
Supply 2 - Dirty fi lter alarm
Automatic
Display only
DI1248
AL246
Return - Dirty fi lter alarm
Automatic
Display only
DI1249
AL247
HEPA Filter 1 alarm
Automatic
Display only
DI1250
AL248
HEPA Filter 2 alarm
Automatic
Display only
DI1251
AL249
Main coil pump 1 overload
Automatic
Immediate main coil shutdown
DI1252
AL250
Main coil pump 2 overload
Automatic
Immediate main coil shutdown
DI1253
AL251
Reheat coil pump 1 overload
Automatic
Immediate reheating coil shutdown
DI1254
AL252
Reheat coil pump 2 overload
Automatic
Immediate reheating coil shutdown
DI1255
AL253
Preheat coil pump 1 overload
Automatic
Immediate preheating coil shutdown
DI1256
AL254
Preheat coil pump 2 overload
Automatic
Immediate preheating coil shutdown
DI1257
AL255
Main coil fl ow switch alarm
Automatic
Immediate main coil shutdown
DI1258
AL256
Reheat coil fl ow switch alarm
Automatic
Immediate reheating coil shutdown
DI1259
AL257
Preheat coil fl ow switch alarm
Automatic
Immediate preheating coil shutdown
DI1260
AL258
Recovery clogged alarm
Automatic
Display only
DI1261
AL259
Reheater alarm
Automatic
Immediate reheating coil shutdown
DI1262
AL260
Preheater alarm
Automatic
Immediate preheating coil shutdown
DI1263
AL261
Alarm - uChiller
Automatic
Immediate uChiller shutdown
DI1264
AL262
Alarm - uChiller offl
ine
Automatic
Display only
DI1265
AL263
Warning - Main coil pump 1 maintenance required
Automatic
Display only
DI1266
AL264
Warning - Main coil pump 2 maintenance required
Automatic
Display only
DI1267
AL265
Warning - Main coil analogue output maintenance required
Automatic
Display only
DI1268
AL266
Warning - Main coil step 1 maintenance required
Automatic
Display only
DI1269
AL267
Warning - Main coil step 2 maintenance required
Automatic
Display only
DI1270
AL268
Warning - Main coil step 3 maintenance required
Automatic
Display only
DI1271
AL269
Warning - Main coil step 4 maintenance required
Automatic
Display only
DI1272
AL270
Warning - Preheating coil pump 1 maintenance required
Automatic
Display only
DI1273
AL271
Warning - Preheating coil pump 2 maintenance required
Automatic
Display only
DI1274
AL272
Warning - Preheating coil analogue output maintenance
required
Automatic
Display only
DI1275
AL273
Warning - Preheating coil step 1 maintenance required
Automatic
Display only
DI1276
AL274
Warning - Preheating coil step 2 maintenance required
Automatic
Display only
DI1277
AL275
Warning - Preheating coil step 3 maintenance required
Automatic
Display only
DI1278
AL276
Warning - Preheating coil step 4 maintenance required
Automatic
Display only
DI1279
AL277
Warning - Reheating coil step 4 maintenance required
Automatic
Display only
DI1280
AL278
Warning - Reheating coil pump 1 maintenance required
Automatic
Display only
DI1281
AL279
Warning - Reheating coil pump 2 maintenance required
Automatic
Display only
DI1282
AL280
Warning - Reheating coil analogue output maintenance
required
Automatic
Display only
DI1283
AL281
Warning - Reheating coil step 1 maintenance required
Automatic
Display only
DI1284
AL282
Warning - Reheating coil step 2 maintenance required
Automatic
Display only
DI1285
AL283
Warning - Reheating coil step 3 maintenance required
Automatic
Display only
DI1286
AL284
Warning - Auxiliary digital output maintenance required
Automatic
Display only
DI1287
AL285
Warning - Auxiliary analogue output maintenance required
Automatic
Display only
DI1288
AL286
Warning - IEC maintenance required
Automatic
Display only
DI1289
AL287
Warning - Unit maintenance required
Automatic
Display only
DI1290
AL288
Alarm - Humifog alarms present
Automatic
Immediate humifog shutdown
DI1291