181
Alarms and signals
k.air +030220981 rel. 1.2 - 01.12.2020
C
ode
D
escription
R
eset
Eff ect
Modbus
AL115
EEV-Emergency closing
Automatic
Immediate compressor shutdown
DI1116
AL116
BLDC-Pressure delta greater than allowed at startup
Automatic
Display only
DI1117
AL117
th - Tune clock not working
Automatic
Display only
DI1118
AL118
BMS offl
ine
Automatic
Unit shutdown / Display only (parameter)
DI1121
AL119
EVD-Selftuning alarm
Automatic
Immediate compressor shutdown
DI1122
AL120
Humisonic-Offl
ine
Automatic
Display only
DI1123
AL121
Humisonic-High humidity
Automatic
Immediate humisonic shutdown
DI1124
AL122
Humisonic-Low humidity
Automatic
Immediate humisonic shutdown
DI1125
AL123
Humisonic-No production
Automatic
Immediate humisonic shutdown
DI1126
AL124
Humisonic-Faulty drain
Automatic
Immediate humisonic shutdown
DI1127
AL125
Humisonic-No water
Automatic
Immediate humisonic shutdown
DI1128
AL126
Humisonic-External signal not correctly connected
Automatic
Immediate humisonic shutdown
DI1129
AL127
Humisonic-Functional test not completed
Automatic
Immediate humisonic shutdown
DI1130
AL128
Humisonic-Autotest failure
Automatic
Immediate humisonic shutdown
DI1131
AL129
Humisonic-EEPROM error
Automatic
Immediate humisonic shutdown
DI1132
AL130
EBM supply fan-Offl
ine
Automatic
Display only
DI1133
AL131
EBM supply fan-Phase Failure (PHA)
Manual
Immediate supply fan shutdown
DI1134
AL132
EBM supply fan-Locked motor (BLK)
Manual
Immediate supply fan shutdown
DI1135
AL133
EBM supply fan-Mains undervoltage (UeLow)
Manual
Immediate supply fan shutdown
DI1136
AL134
EBM supply fan-Mains overvoltage (UeHigh)
Manual
Immediate supply fan shutdown
DI1137
AL135
EBM supply fan-DC - link overvoltage (UzHigh)
Manual
Immediate supply fan shutdown
DI1138
AL136
EBM supply fan-DC - link undervoltage (UzLow)
Manual
Immediate supply fan shutdown
DI1139
AL137
EBM supply fan-Motor overheated (TFM)
Manual
Immediate supply fan shutdown
DI1140
AL138
EBM supply fan-Internal electronics overheated (TFEI)
Manual
Immediate supply fan shutdown
DI1141
AL139
EBM supply fan-Power mod overheated (TFE)
Manual
Immediate supply fan shutdown
DI1142
AL140
EBM supply fan-Hall sensor error (HLL)
Manual
Immediate supply fan shutdown
DI1143
AL141
EBM supply fan-Communication error (SKF)
Manual
Immediate supply fan shutdown
DI1144
AL142
EBM supply fan-Output stage high temperature (TE_high)
Automatic
Immediate supply fan shutdown
DI1145
AL143
EBM supply fan-Internal electronics high temperature (TEI_high) Automatic
Immediate supply fan shutdown
DI1146
AL144
EBM supply fan-Motor high temperature (TM_high)
Automatic
Immediate supply fan shutdown
DI1147
AL145
EBM supply fan-DC - link voltage low (UzLow)
Automatic
Immediate supply fan shutdown
DI1148
AL146
EBM supply fan-Power limitation engaged (P_Limit)
Automatic
Immediate supply fan shutdown
DI1149
AL147
EBM supply fan-Current limitation engaged (I_Limit)
Automatic
Immediate supply fan shutdown
DI1150
AL148
EBM supply fan-Brake mode (Brake)
Automatic
Immediate supply fan shutdown
DI1151
AL149
EBM supply fan-Cable break at set value analogue input (Cable
break)
Automatic
Immediate supply fan shutdown
DI1152
AL150
EBM supply fan-Ice protection function active (Ice)
Automatic
Immediate supply fan shutdown
DI1153
AL151
EBM supply fan-Heating enabled, the motor should not start
Automatic
Immediate supply fan shutdown
DI1154
AL152
EBM supply fan-Actual speed is less than limit speed for running
monitor (n_Low)
Automatic
Immediate supply fan shutdown
DI1155
AL153
EBM supply fan-DC - link voltage high (UzHigh)
Automatic
Immediate supply fan shutdown
DI1156
AL154
EBM supply fan-Supply voltage high (UeHigh)
Automatic
Immediate supply fan shutdown
DI1157
AL155
EBM supply fan-Line impedance too high (L_high)
Automatic
Immediate supply fan shutdown
DI1158
AL156
EBM return fan-Offl
ine
Automatic
Display only
DI1159
AL157
EBM return fan-Phase Failure (PHA)
Manual
Immediate return fan shutdown
DI1160
AL158
EBM return fan-Locked motor (BLK)
Manual
Immediate return fan shutdown
DI1161
AL159
EBM return fan-Mains undervoltage (UeLow)
Manual
Immediate return fan shutdown
DI1162
AL160
EBM return fan-Mains overvoltage (UeHigh)
Manual
Immediate return fan shutdown
DI1163
AL161
EBM return fan-DC - link overvoltage (UzHigh)
Manual
Immediate return fan shutdown
DI1164
AL162
EBM return fan-DC - link undervoltage (UzLow)
Manual
Immediate return fan shutdown
DI1165
AL163
EBM return fan-Motor overheated (TFM)
Manual
Immediate return fan shutdown
DI1166
AL164
EBM return fan-Internal electronics overheated (TFEI)
Manual
Immediate return fan shutdown
DI1167
AL165
EBM return fan-Power mod overheated (TFE)
Manual
Immediate return fan shutdown
DI1168
AL166
EBM return fan-Hall sensor error (HLL)
Manual
Immediate return fan shutdown
DI1169
AL167
EBM return fan-Communication error (SKF)
Manual
Immediate return fan shutdown
DI1170
AL168
EBM return fan-Output stage high temperature (TE_high)
Automatic
Immediate return fan shutdown
DI1171
AL169
EBM return fan-Internal electronics high temperature (TEI_high)
Automatic
Immediate return fan shutdown
DI1172
AL170
EBM return fan-Motor high temperature (TM_high)
Automatic
Immediate return fan shutdown
DI1173
AL171
EBM return fan-DC - link voltage low (UzLow)
Automatic
Immediate return fan shutdown
DI1174
AL172
EBM return fan-Power limitation engaged (P_Limit)
Automatic
Immediate return fan shutdown
DI1175
AL173
EBM return fan-Current limitation engaged (I_Limit)
Automatic
Immediate return fan shutdown
DI1176
AL174
EBM return fan-Brake mode (Brake)
Automatic
Immediate return fan shutdown
DI1177
AL175
EBM return fan-Cable break at set value analogue input
(Cable break)
Automatic
Immediate return fan shutdown
DI1178