71
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
IE
C
I001
IEC: PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1646
AV3141
IEC: PID parameters - Integral time
120
0
999
-
R/W HR1647
PIV3142
I005
IEC: Return humidity activation threshold
75.0
0.0
100.0
%rh
R/W HR1648
AV3143
IEC: Return humidity activation diff erential
2.0
0.0
20.0
%rh
R/W HR1649
AV3144
I010
IEC: Exhaust humidity limit threshold
95.0
0.0
100.0
%rh
R/W HR1650
AV3145
IEC: Exhaust humidity limit proportional gain
10.0
0.0
999.9
-
R/W HR1651
AV3146
IEC: Exhaust humidity limit integral time
60
0
999
s
R/W HR1652
PIV3147
I015
IEC: Fresh air damper maximum limitation
0.0
0.0
100.0
%
R/W HR1653
AV3148
Tab. 9.y
Note:
if an exhaust humidity probe is installed, it is recommended to use a type with limits extended to 0 to 100%
9.13 Humidity control
Humidity control can be activated by enabling the humidifi er and/or the dehumidifi cation option, both available on screen
Ac04. Control is carried out based on the selected probe (screen Ac32), supply, return or room. When the unit is turned on, the
humidity regulation can be delayed by a confi gurable time (mask Ac32) compare to the temperature regulation.
Control can be performed using the relative humidity value or the absolute humidity value.
To assist commissioning, the set point will still be the relative humidity value, and k.air will then calculate the equivalent in abso-
lute humidity by taking into account the temperature set point; the result is shown on the info screen.
With the humidifi er and dehumidifi cation enabled, the unit has both settings available and independent of the active mode,
heating or cooling. The humidity changeover function can be set on screen Ac36.
30220980_195_R01
RegPrb (rh%)
HumSetp
ChgDT
Band
ChgDT
Time
Mode
Hum
Hum
Dehum
Key
RegPrb
Control probe
HumSetp
Humidity set point
Band
Changeover band
ChgDT
Changeover delay
Fig. 9.ab
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Aa75 Unit setpoints - Humidity - Cooling - Economy - Setpoint
60.0
LowLimVal
HiLimVal
%rh
R/W HR1161
AV2671
Unit setpoints - Humidity - Heating - Economy - Setpoint
40.0
LowLimVal
HiLimVal
%rh
R/W HR1162
AV2672
Unit setpoints - Humidity - Cooling - Economy - Low limit value
50.0
0.0
HiLimVal
%rh
R/W HR1163
AV2673
Unit setpoints - Humidity - Heating - Economy - Low limit value
35.0
0.0
HiLimVal
%rh
R/W HR1164
AV2674
Unit setpoints - Humidity - Cooling - Economy - High limit value
65.0
LowLimVal
100.0
%rh
R/W HR1165
AV2675
Unit setpoints - Humidity - Heating - Economy - High limit value
45.0
LowLimVal
100.0
%rh
R/W HR1166
AV2676
Aa78 Unit setpoints - Humidity - Cooling - Pre- comfort - Setpoint
55.0
LowLimVal
HiLimVal
%rh
R/W HR1167
AV2677
Unit setpoints - Humidity - Heating - Pre-comfort - Setpoint
45.0
LowLimVal
HiLimVal
%rh
R/W HR1168
AV2678
Unit setpoints - Humidity - Cooling - Pre- comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1169
AV2679
Unit setpoints - Humidity - Heating - Pre-comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1170
AV2680
Unit setpoints - Humidity - Cooling - Pre- comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1171
AV2681
Unit setpoints - Humidity - Heating - Pre-comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1172
AV2682
Aa81 Scheduler: confi guration - Enabled
FALSE 0
1
-
R
CS064
BV64
Unit setpoints - Humidity - Cooling - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1173
AV2683
Unit setpoints - Humidity - Heating - Comfort - Setpoint
50.0
LowLimVal
HiLimVal
%rh
R/W HR1174
AV2684
Unit setpoints - Humidity - Cooling - Comfort - Low limit value
40.0
0.0
HiLimVal
%rh
R/W HR1175
AV2685
Unit setpoints - Humidity - Heating - Comfort - Low limit value
30.0
0.0
HiLimVal
%rh
R/W HR1176
AV2686
Unit setpoints - Humidity - Cooling - Comfort - High limit value
60.0
LowLimVal
100.0
%rh
R/W HR1177
AV2687
Unit setpoints - Humidity - Heating - Comfort - High limit value
55.0
LowLimVal
100.0
%rh
R/W HR1178
AV2688