26
User interface
k.air +030220981 rel. 1.2 - 01.12.2020
Room temp.: 25°C
Unit set point Qc01
Air quality: 800 ppm
Regulation probe
30220980_075_R01
Fig. 4.c
Possible unit operating modes/status:
I
D
Unit status
D
escription
0
OFF ALRM
Off from alarm
1
OFF BMS
Off from BMS
2
OFF BAND
Off by time band
3
OFF IN.DIG.
Off from digital input
4
OFF KEYPAD
Off from keypad
5
OFF FAN
Off due to no ventilation
6
OFF FLOW
Off due to no fl ow
7
OFF FROST
Frost protection with unit OFF
8
ON
Unit starting
9
WARM UP
Warm up
10
HEAT
Unit ON in heating mode
11
COOL
Unit ON in cooling mode
12
MANUAL ON
Starting with manual mode active(*)
13
WARM UP MAN.
Warm up with manual mode active(*)
14
HEAT MAN
Heating with manual mode active(*)
15
COOL MAN
Cooling with manual mode active(*)
16
REC. DEFROST
Defrost on heat recovery
17
DEFROST DX
Defrost on direct expansion circuit
18
FROST
Frost protection
19
C. PROBE ERR.
Control probe error
20
SHUTDOWN
Shutting down
22
DEHUMIDIFICATION
Dehumidifi cation active
23
GENERIC CON.
Generic control active (no temp. control)
24
GEN. CON. MAN.
Generic control active (no temp. control) with manual mode active(*)
31
LOW SUPPLY T
Minimum supply limit control
32
HIGH SUPPLY T
Maximum supply limit control
33
HIGH H SAT
High humidity control (VDI)
34
START INACT.
Start due to inactivity (VDI)
Tab. 4.b
(*) at least 1 device controlled in manual mode. See “Functions”.
4.4
P
rogramming mode
The parameters can be set on the user terminal. Access to the parameters depends on the level: User (password = 0000), Service
(password = 1234) and Manufacturer (password = 5678). Press Prg to access the main menu.
Z. Wizard
A. Unit
B. Fans
1/14
30220980_076_R01
Fig. 4.d