Supervisor variable table
k.air +030220981 rel. 1.2 - 01.12.2020
Variable
D
escription
D
im Modbus
BAC
net
Al_WrkHrs_ReturnFan.Active
Warning - Return fan maintenance required - Alarm status
1
DI1098
BV1326
Al_WrkHrs_ThrmlWheel.Active
Warning - Thermal wheel maintenance required - Alarm
status
1
DI1099
BV1327
AuxPrb_1.Alrm_R
Auxiliary probe 1 - Alarm probe broken or disconnected
1
DI110
BV568
Al_WrkHrs_DirtyFilt.Active
Warning - Filters maintenance required - Alarm status
1
DI1100
BV1328
Al_DirtyFiltByDin.Active
Common - Dirty fi lters alarm - Alarm status
1
DI1101
BV1329
Al_WrkHrs_Comp.Active
Warning - Compressor maintenance required - Alarm status
1
DI1102
BV1330
Al_HiRatioP_BLDC.Active
Compressor envelope-High compression ratio - Alarm status
1
DI1103
BV1331
Al_DscgHiP_BLDC.Active
Compressor envelope-High discharge pressure - Alarm status 1
DI1104
BV1332
Al_HiCurr_BLDC.Active
Compressor envelope-High motor current - Alarm status
1
DI1105
BV1333
Al_SuctHiP_BLDC.Active
Compressor envelope-High suction pressure - Alarm status
1
DI1106
BV1334
Al_LowRatioP_BLDC.Active
Compressor envelope-Low compression ratio - Alarm status
1
DI1107
BV1335
Al_LowDeltaP_BLDC.Active
Compressor envelope-Low diff erential pressure - Alarm status 1
DI1108
BV1336
Al_LowDscgP_BLDC.Active
Compressor envelope-Low discharge pressure - Alarm status
1
DI1109
BV1337
AuxPrb_2.Enable_W
Auxiliary probe 2 - Enable input
1
DI111
BV569
Al_LowSuctP_BLDC.Active
Compressor envelope-Low suction pressure - Alarm status
1
DI1110
BV1338
Al_HiDscgTemp_BLDC.Active
Compressor envelope -High discharge temperature -
Alarm status
1
DI1111
BV1339
Al_LOP_EVD_Emb.Active
EVD-LOP - Alarm status
1
DI1112
BV1340
Al_MOP_EVD_Emb.Active
EVD-MOP - Alarm status
1
DI1113
BV1341
Al_HiCondTemp_EVD_Emb.Active
EVD-High condensing temperature - Alarm status
1
DI1114
BV1342
Al_LowSuctTemp_EVD_Emb.Active
EVD-Low suction temperature - Alarm status
1
DI1115
BV1343
Al_EmergClos_EVD_Emb.Active
EVD-Emergency closing - Alarm status
1
DI1116
BV1344
Al_DisStartDp_BLDC.Active
BLDC-Delta pressure greater than the allowable at startup -
Alarm status
1
DI1117
BV1345
Al_ThTune_ClkBrd.Active
th - Tune clock not working - Alarm status
1
DI1118
BV1346
AuxPrb_2.Confi gured_R
Auxiliary probe 2 - Analog input confi gured
1
DI112
BV570
Al_BMS_Offl
ine.Active
BMS offl
ine - Alarm status
1
DI1121
BV1347
Al_Selftuning_EVD_Emb.Active
EVD-Selftuning alarm - Alarm status
1
DI1122
BV1348
Al_Offl
ine_Humisonic.Active
Humisonic-Offl
ine - Alarm status
1
DI1123
BV1349
Al_HiHum_Humisonic.Active
Humisonic-High humidity - Alarm status
1
DI1124
BV1350
Al_LowHum_Humisonic.Active
Humisonic-Low humidity - Alarm status
1
DI1125
BV1351
Al_NoProd_Humisonic.Active
Humisonic-No production - Alarm status
1
DI1126
BV1352
Al_FaultyDrn_Humisonic.Active
Humisonic-Faulty drain - Alarm status
1
DI1127
BV1353
Al_Wmissing_Humisonic.Active
Humisonic-Missing water - Alarm status
1
DI1128
BV1354
Al_ExtSignal_Humisonic.Active
Humisonic-External signal not correctly connected - Alarm status 1
DI1129
BV1355
AuxPrb_2.PrbOk_R
Auxiliary probe 2 - Probe working correctly
1
DI113
BV571
Al_Functest_Humisonic.Active
Humisonic-Functional test not executed - Alarm status
1
DI1130
BV1356
Al_Autotest_Humisonic.Active
Humisonic-Autotest failure - Alarm status
1
DI1131
BV1357
Al_EEPROM_Err_Humisonic.Active
Humisonic-EEPROM error - Alarm status
1
DI1132
BV1358
Al_Offl
ine_EBM_SupplyFan.Active
EBM supply fan-Offl
ine - Alarm status
1
DI1133
BV1359
Al_PhaseFault_EBM_SupplyFan.Active
EBM supply fan-Phase Failure (PHA) - Alarm status
1
DI1134
BV1360
Al_MotBlocked_EBM_SupplyFan.Active
EBM supply fan-Locked motor (BLK) - Alarm status
1
DI1135
BV1361
Al_MainsUnderV_EBM_SupplyFan.Active
EBM supply fan-Mains undervoltage (UeLow) - Alarm status
1
DI1136
BV1362
Al_MainsOverV_EBM_SupplyFan.Active
EBM supply fan-Mains overvoltage (UeHigh) - Alarm status
1
DI1137
BV1363
Al_DClinkOverV_EBM_SupplyFan.Active
EBM supply fan-DC - link overvoltage (UzHigh) - Alarm status
1
DI1138
BV1364
Al_DClinkUnderV_EBM_SupplyFan.Active
EBM supply fan-DC - link undervoltage (UzLow) - Alarm status 1
DI1139
BV1365
AuxPrb_2.Alrm_R
Auxiliary probe 2 - Alarm probe broken or disconnected
1
DI114
BV572
Al_MotSuperHeating_EBM_SupplyFan.Active
EBM supply fan-Motor overheated (TFM) - Alarm status
1
DI1140
BV1366
Al_IntCircSuperHeat_EBM_SupplyFan.Active
EBM supply fan-Electronics interior overheated (TFEI) - Alarm status 1
DI1141
BV1367
Al_OutStageSuperHeat_EBM_SupplyFan.Active
EBM supply fan-Power mod overheated (TFE) - Alarm status
1
DI1142
BV1368
Al_HallSenErr_EBM_SupplyFan.Active
EBM supply fan-Hall sensor error (HLL) - Alarm status
1
DI1143
BV1369
Al_CommunicationErr_EBM_SupplyFan.Active
EBM supply fan-Communication error (SKF) - Alarm status
1
DI1144
BV1370
Al_OutStageHighTemp_EBM_SupplyFan.Active
EBM supply fan-Output stage temperature high (TE_high) -
Alarm status
1
DI1145
BV1371
Al_InternCircHighTemp_EBM_SupplyFan.Active EBM supply fan-Electronics interior temperature high
(TEI_high) - Alarm status
1
DI1146
BV1372
Al_MotHighTemp_EBM_SupplyFan.Active
EBM supply fan-Motor temperature high (TM_high) - Alarm status 1
DI1147
BV1373
Al_DClinkV_Low_EBM_SupplyFan.Active
EBM supply fan-DC - link voltage low (UzLow) - Alarm status
1
DI1148
BV1374
Al_LimMainsPwr_EBM_SupplyFan.Active
EBM supply fan-Power limitation engaged (P_Limit) - Alarm status 1
DI1149
BV1375
AuxPrb_3.Enable_W
Auxiliary probe 3 - Enable input
1
DI115
BV573
Al_LimMainsA_EBM_SupplyFan.Active
EBM supply fan-Current limitation engaged (I_Limit) - Alarm status 1
DI1150
BV1376
Al_BrakeMode_EBM_SupplyFan.Active
EBM supply fan-Brake mode (Brake) - Alarm status
1
DI1151
BV1377
Al_CableBreak_EBM_SupplyFan.Active
EBM supply fan-Cable break at set value analogue input
(Cable break) - Alarm status
1
DI1152
BV1378