113
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ad03
Fresh air damper manual mode enable
FALSE
0
1
-
R/W CS184
BV184
Fresh air damper manual mode value
10.0
0.0
100.0
%
R/W HR1041
AV2551
For mask usage
0
0
100
%
R/W HR1042
PIV2552
Ad06
Mixing damper manual mode enable
FALSE
0
1
-
R/W CS185
BV185
Mixing damper manual mode value
10.0
0.0
100.0
%
R/W HR1043
AV2553
For mask usage
-
0
100
%
R/W HR1044
PIV2554
Ad09
Exhaust air damper manual mode enable
FALSE
0
1
-
R/W CS186
BV186
Exhaust air damper manual mode value
0.0
0.0
100.0
%
R/W HR1045
AV2555
For mask usage
0
0
100
%
R/W HR1046
PIV2556
Ad12
Bypass damper manual mode enable
FALSE
0
1
-
R/W CS187
BV187
Bypaas damper manual mode value
10.0
0.0
100.0
-
R/W HR1047
AV2557
For mask usage
-
0
100
%
R/W HR1048
PIV2558
Ad15
Supply fan manual mode enable
FALSE
0
1
-
R/W CS188
BV188
For mask usage
-
0
3
-
R/W HR1049
PIV2559
Supply fan manual mode value
10.0
0.0
100.0
%
R/W HR1050
AV2560
For mask usage
-
0
100
-
R/W HR1051
PIV2561
Ad18
Return fan manual mode enable
FALSE
0
1
-
R/W CS189
BV189
For mask usage
-
0
3
-
R/W HR1052
PIV2562
Return fan manual mode value
10.0
0.0
100.0
%
R/W HR1053
AV2563
For mask usage
-
0
100
-
R/W HR1054
PIV2564
Ad21
Pre heating coil manual mode enable
FALSE
0
1
-
R/W CS190
BV190
Pre heating coil manual mode value
0.0
0.0
100.0
%
R/W HR1055
AV2565
Ad24
Main coil manual mode enable
FALSE
0
1
-
R/W CS191
BV191
Main coil manual mode value
0.0
0.0
100.0
%
R/W HR1056
AV2566
Ad27
Post heating coil manual mode enable
FALSE
0
1
-
R/W CS192
BV192
Post heating coil manual mode value
0.0
0.0
100.0
%
R/W HR1057
AV2567
Ad30
Compressor manual mode enable
FALSE
0
1
-
R/W CS193
BV193
Compressor manual mode value
10.0
0.0
100.0
%
R/W HR1058
AV2568
Ad33
Compressor manual mode enable
FALSE
0
1
-
R/W CS193
BV193
For mask usage
0
0
100
%
R/W HR1059
PIV2569
Ad36
Humidifi er manual mode enable
FALSE
0
1
-
R/W CS194
BV194
Humidifi er manual mode value
30.0
0.0
100.0
-
R/W HR1060
AV2570
Ad39
Bypass damper manual mode enable
FALSE
0
1
-
R/W CS187
BV187
Thermal wheel manual mode value
10.0
0.0
100.0
%
R/W HR1061
AV2571
Ad42
Auxiliary Regulation 1 - Manual mode enabled
FALSE
0
1
-
R/W CS266
BV266
Auxiliary Regulation 1 - Modulating: Manual mode value
0.0
0.0
100.0
-
R/W HR1596
AV3091
Auxiliary Regulation 1 - Dout: Manual mode value
FALSE
0
1
-
R/W CS267
BV267
Ad45
Auxiliary Regulation 2 - Manual mode enabled
FALSE
0
1
-
R/W CS273
BV273
Auxiliary Regulation 2 - Modulating: Manual mode value
0.0
0.0
100.0
-
R/W HR1610
AV3105
Auxiliary Regulation 2 - Dout: Manual mode value
FALSE
0
1
-
R/W CS274
BV274
Ad48
Auxiliary Regulation 3 - Manual mode enabled
FALSE
0
1
-
R/W CS280
BV280
Auxiliary Regulation 3 - Modulating: Manual mode value
0.0
0.0
100.0
-
R/W HR1624
AV3119
Auxiliary Regulation 3 - Dout: Manual mode value
FALSE
0
1
-
R/W CS281
BV281
Ad51
Auxiliary Regulation 4 - Manual mode enabled
FALSE
0
1
-
R/W CS287
BV287
Auxiliary Regulation 4 - Modulating: Manual mode value
0.0
0.0
100.0
-
R/W HR1638
AV3133
Auxiliary Regulation 4 - Dout: Manual mode value
FALSE
0
1
-
R/W CS288
BV288
Ae01
Unit - Working hours
0
0
99
h
R
IR385
PIV3762
Unit - Working hours
0
0
99
h
R
IR385
PIV3762
Unit - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1395
PIV2903
Unit - Working hours left to the maintenance
-
0
99
h
R
IR387
PIV3763
Unit - Working hours reset
-
0
1
-
R/W HR1396
PIV2904
Ae03
Supply Fan - Working hours
0
0
99
h
R
IR389
PIV3764
Supply Fan - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1397
PIV2905
Supply Fan - Working hours left to the maintenance
-
0
99
h
R
IR391
PIV3765
Supply Fan - Working hours reset
-
0
1
-
R/W HR1398
PIV2906
Ae06
Return Fan - Working hours
0
0
99
h
R
IR393
PIV3766
Return Fan - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1399
PIV2907
Return Fan - Working hours left to the maintenance
-
0
99
h
R
IR395
PIV3767
Return Fan - Working hours reset
-
0
1
-
R/W HR1400
PIV2908
Ae09
Dirty fi lters - Working hours
0
0
99
h
R
IR397
PIV3768
Dirty fi lters - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1401
PIV2909
Dirty fi lters - Working hours left to the maintenance
-
0
99
h
R
IR399
PIV3769
Dirty fi lters - Working hours reset
-
0
1
-
R/W HR1402
PIV2910
Ae12
Thermal wheel - Working hours
0
0
99
h
R
IR401
PIV3770
Thermal wheel - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1403
PIV2911
Thermal wheel - Working hours left to the maintenance
-
0
99
h
R
IR403
PIV3771
Thermal wheel - Working hours reset
-