17
Hardware installation
k.air +030220981 rel. 1.2 - 01.12.2020
3.4
P
ower supply
30220980_018_R01
24 Vac
230 Vac
2.5 A T
28...36 Vdc
2.5 A T
–
+
AC
DC
G
G0
Vbat
J1
G
G0
Vbat
J1
The following fi gure shows the power supply connection diagram. Use a class II
safety transformer with protection against short circuits and overload.
Vca
P
(Vca)
Vcc
P
(Vcc)
24 Vac (+ 10/-15%),
50/60 Hz to be
protected by an
external 2.5 A (T) fuse
k.Air mini 30 VA
28-36 Vdc (-20/+10%)
to be protected
by an external
2.5 A (T) fuse
k.Air mini
12 W
k.Air large 45 VA
k.Air large 30 W
Tab. 3.b
Fig. 3.h
Important:
• if the Ethernet connection is used, the transformer secondary must be connected to earth;
• a power supply voltage other than that specifi ed may seriously damage the controller;
• it is recommended to separate the power supply to the controller and the terminal from the power supply to the other
electrical devices (contactors and other electromechanical components) inside the electrical panel.
3.5 p
GD
E terminal connection
k.air mini
Use the accessory cable P/N S90CONN0S0, as shown in the fi gure. The maximum distance allowed between controller and
terminal is 10 m.
Note
: for connection cable lengths > 10 m or to connect multiple terminals, use the TCONN6J000 accessory. See manual
+0300057EN.
L < 50 m
cavo telefonico S90CONN0S0
S90CONN0S0 telephone cable
30220980_019_R01
bianco-white/blu-blue: +Vterm
nero-black/giallo-yellow: GND
rosso/red: –
verde/green: +
bianco/white
nero/black
rosso/red
blu/blue
giallo/yellow
verde/green
k.Air mini
pGD1
Fig. 3.i
k.air large
Use the accessory cable P/N S90CONN00*0, connected as shown in the fi gure. The maximum distance allowed between con-
troller and terminal is 50 m.
Note
:
for connection cable lengths > 50 m or to connect multiple terminals, use the TCONN6J000 accessory. See manual
+0300057EN.
J10
Tx/Rx
J11 pLAN
GND
+
L < 50 m
cavo telefonico
telephone cable
30220980_020_R01
k.Air large
pGD1
Fig. 3.j