124
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
CO
M
PR
E
SSOR
Ua27
Defrost: delay time before change over
20
0
900
s
R/W HR1538
PIV3039
Defrost: delay time after change over
10
0
900
s
R/W HR1539
PIV3040
Ua30
Fans request during evaporator defrost
3
0
3
%
R/W HR1540
PIV3041
Fans request during evaporator defrost
30.0
0.0
100.0
%
R/W HR1541
AV3042
Fans request during evaporator defrost
0
0
100
%
R/W HR1542
PIV3043
Fans request during evaporator defrost: dripping
2
0
3
%
R/W HR1543
PIV3044
Fans request during evaporator defrost: dripping
30.0
0.0
100.0
%
R/W HR1544
AV3045
Fans request during evaporator defrost: dripping
100
0
100
%
R/W HR1545
PIV3046
Fans request during evaporator defrost: post dripping
2
0
3
%
R/W HR1546
PIV3047
Fans request during evaporator defrost: post dripping
30.0
0.0
100.0
%
R/W HR1547
AV3048
Fans request during evaporator defrost: post dripping
100
0
100
%
R/W HR1548
PIV3049
Ua33
Disable Low supply temperature alarm
TRUE
0
1
-
R/W CS250
BV250
Ua36
Enable compressor during night ventilation
FALSE
0
1
-
R/W CS251
BV251
Ub01
BLDC informations - Compressor power request [%]
-
0.0
100.0
-
R
IR600
AV3914
BLDC informations - Required speed to PowerPlus [%]
-
-999.9
999.9
-
R
IR601
AV3915
Inverter Power Plus Info - Current rotor speed [rps]
-
-999.0
999.0
-
R
IR240
AV3628
BLDC informations - Managing test mode
-
0
1
-
R
DI764
BV1222
BLDC informations - Working zone 1c - max speed 90 rps (Siam only)
-
0
1
-
R
DI765
BV1223
BLDC informations - Show pressure equalization status (blinking)
-
0
1
-
R
DI766
BV1224
Ub02
BLDC informations - Discharge pressure relative [bar]
-
-99.9
99.9
bar
R
IR602
AV3916
BLDC informations - Suction pressure relative [bar]
-
-99.9
99.9
bar
R
IR603
AV3917
BLDC informations - Current envelope zone
-
0
9
-
R
IR604
IV3918
BLDC informations - Out of envelop timing countdown
-
0
32767
s
R
IR605
IV3919
Ub03
BLDC informations - Current delta pressure
-
-999.9
999.9
bar
R
IR606
AV3920
BLDC informations - Current pressure ratio
-
0.0
999.9
-
R
IR607
AV3921
BLDC informations - Show low pressure diff erence condition
-
0
1
-
R
DI767
BV1225
BLDC informations - Low pressure diff erence alarm timing countdown
-
0
999
s
R
IR608
IV3922
Ub04
BLDC informations - Current discharge temperature
-
-999.9
999.9
°C
R
IR609
AV3923
BLDC informations - High discharge temperature zone
-
0
9
-
R
IR610
IV3924
BLDC informations - Envelope Type: Siam compressor
-
0
1
-
R
DI768
BV1226
BLDC informations - Show active value of discharge temp. alarm limit -
-999.9
999.9
-
R
IR611
AV3925
Ub05
BLDC informations - Current discharge superheat
-
-999.9
999.9
K
R
IR612
AV3926
BLDC to EVD parameters - EVD regulation subtype
-
0
9
-
R
IR237
IV3625
Ub06
BLDC envelope confi guration - Max. permitted Delta P to start up [bar]
9.0
0.0
999.9
bar
R/W HR1856
AV3338
Ub07
BLDC envelope confi guration - By-pass equalization solenoid valve
enable
FALSE
0
1
-
R/W CS456
BV455
BLDC envelope confi guration - Maximum time of EVD propening to
equalize pressure
10
0
999
s
R/W HR1857
IV3339
BLDC envelope confi guration - Preopening of EVD in case of prestart
to equalize pressure
50
0
100
-
R/W HR1858
IV3340
Ub08
BLDC envelope confi guration - Min. variation of Delta P to considered
compressor started [bar]
0.2
0.0
2.0
bar
R/W HR1859
AV3341
BLDC envelope confi guration - Delay to check increasing DeltaP to
validate compressor started
15
10
99
s
R/W HR1860
IV3342
Ub09
BLDC envelope confi guration - Restart delay after a start failure
30
1
360
s
R/W HR1861
IV3343
BLDC envelope confi guration - Max Number of starting attempts
5
0
9
-
R/W HR1862
IV3344
Ub10
BLDC envelope confi guration - Start up speed
50.0
20.0
120.0
-
R/W HR1863
AV3345
BLDC envelope confi guration - Max speed custom (rps)
120.0
0.0
999.9
-
R/W HR1864
AV3346
BLDC envelope confi guration - Min speed custom (rps)
20.0
0.0
99.9
-
R/W HR1865
AV3347
Ub11
BLDC envelope confi guration - Max. decrease speed rate (in regula-
tion) [rps/s]
1.6
0.1
9.9
-
R/W HR1866
AV3348
BLDC envelope confi guration - Max. increase speed rate (in regula-
tion) [rps/s]
1.0
0.1
9.9
-
R/W HR1867
AV3349
BLDC envelope confi guration - Decrease max speed rate (= max
admitted value, to stop compressor) [rps/s]
2.0
0.0
9.9
-
R/W HR1868
AV3350
Ub12
BLDC envelope confi guration - Decrease speed rate (to come back
inside envelope) [rps/s]
0.8
0.1
9.9
-
R/W HR1869
AV3351
BLDC envelope confi guration - Min speed permitted to control com-
pressor working conditions inside envelop
20.0
0.0
99.9
-
R/W HR1870
AV3352
Ub13
BLDC envelope confi guration - Out of envelop alarm delay time
60
0
32000
s
R/W HR1871
IV3353
BLDC envelope confi guration - Low Delta P alarm delay
60
0
32000
s
R/W HR1872
IV3354
Ub14
BLDC envelope confi guration - Suction sat.temp. threshold from zone
1b (Max120rps) to zone 1c (Max90rps SIAM only)
12.0
0.0
999.9
°C
R/W HR1873
AV3355
BLDC envelope confi guration - Max Speed in rps for Zone 1c (SIAM
Scroll) N.B.: integer rps!
90
20
120
-
R/W HR1874
IV3356
Ub15
BLDC envelope confi guration - Enable MOP control in low compres-
sion ratio condition
TRUE
0
1
-
R/W CS457
BV456
BLDC envelope confi guration - Speed up mode enable to control
zones 5, 6, 7, 8 (to come back into zone 1)
FALSE
0
1
-
R/W CS458
BV457