
76
Functions
k.air +030220981 rel. 1.2 - 01.12.2020
9.17 Heat recovery
The heat recovery unit is an additional device that provides free energy. If the conditions are favourable, the heat contained in
the exhaust air is recovered and transferred to the primary air, so as to pre-heat or pre-cool it. The heat recovery unit, if enabled
on Ac01, is always available as a control stage in the main sequential temperature control PID. However, the freecooling/freehe-
ating conditions must not be true at the same time, as these are mutually exclusive.
k.air can manage the following types of heat recovery unit:
Type
S
ignal/actuator
C
ontrol
Cross-fl ow
On/off bypass
The bypass damper is activated when the return/room temperature is below the set point by a set
delta in cooling mode, or when the return/room temperature is above the set point by a set delta in
heating mode
Modulating bypass
The bypass damper is managed by the heat recovery function when the freecooling/freeheating
conditions are not present. The modulation signal is set by the main sequential temperature control
PID.
Wheel
Rotor modulation
signal
The bypass damper is managed by the heat recovery function when the freecooling/freeheating
conditions are not present. The modulation signal is set by the main sequential temperature control
PID.
Double on/off
coil
Pump on/off signal
The on/off signal is activated when the return/room temperature is below the set point by a set
delta in cooling mode, or when the return/room temperature is above the set point by a set delta in
heating mode
Double modu-
lating coil
Modulating pump
signal
The modulation signal is set by the main sequential temperature control PID. In the I/O menu, the
digital output used to enable the analogue signal can be set.
Tab. 9.af
When heat recovery is enabled, an input can be selected for signalling if the heat recovery unit is clogged. This is signal-only,
with no eff ect on control.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ac01
Fans type (0: On/Off ; 1: 3 speeds; 2: Modulating; 3: Modbus RTU)
2
0
3
-
R/W HR1292
PIV2800
Enable return fan
FALSE 0
1
-
R/W CS225
BV225
Heating exchanger type
0
0
4
-
R/W HR1293
PIV2801
For mask usage
-
0
1
-
R
DI696
BV1154
Return fan confi guration error
-
0
1
-
R
DI697
BV1155
Tab. 9.ag
Note:
also see the chapter on heat recovery unit defrost.
The activation temperature diff erentials are needed to determine how effi
cient it is to use freecooling/freeheating, considering
that the greater the diff erence between the outside air temperature and the return temperature, the more effi
cient the action
will be.
For units with modulating fresh air dampers, the conditions for activating freecooling/freeheating are the same, however free-
cooling/freeheating is considered as the fi rst stage in cascade control. The controller adjusts the modulating fresh air damper (in
sync with the mixing damper), and the bypass damper, if fi tted, is opened completely.
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
HE
A
T
R
E
CO
VE
RY
E001
Heat recovery delta for bypass damper in cooling mode
4.0
- 99.9
99.9
K
R/W HR1458
AV2966
Heat recovery delta for bypass damper in heating mode
4.0
- 99.9
99.9
K
R/W HR1459
AV2967
E004
Heat exchanger PID parameters - Proportional gain
8.0
0.0
999.9
-
R/W HR1460
AV2968
Heat exchanger PID parameters - Integral time
120
0
999
-
R/W HR1461
PIV2969
E008
Heating exchanger type
0
0
4
-
R
HR1293
PIV2801
Bypass damper: minimum opening threshold
-5.0
- 50.0
30.0
°C
R/W HR1462
AV2970
Bypass damper: maximum opening threshold
- 10.0
- 50.0
30.0
°C
R/W HR1463
AV2971
E012
Minimum time between heat exchanger defrost
15
0
999
min
R/W HR1464
PIV2972
Maximum defrost heat exchanger duration
15
0
999
min
R/W HR1466
PIV2973
E016
Exhaust temperature threshold for defrost
20.0
- 50.0
90.0
°C
R/W HR1468
AV2974
E020
Stratifi cation correction factor of the room temperature
0.0
0.0
10.0
K
R/W HR1469
AV2975
Tab. 9.ah
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......