182
Alarms and signals
k.air +030220981 rel. 1.2 - 01.12.2020
C
ode
D
escription
R
eset
Eff ect
Modbus
AL176
EBM return fan-Ice protection function active (Ice)
Automatic
Immediate return fan shutdown
DI1179
AL177
EBM return fan-Heating enabled, the motor should not start
Automatic
Immediate return fan shutdown
DI1180
AL178
EBM return fan-Actual speed is less than limit speed for running
monitor (n_Low)
Automatic
Immediate return fan shutdown
DI1181
AL179
EBM return fan-DC - link voltage high (UzHigh)
Automatic
Immediate return fan shutdown
DI1182
AL180
EBM return fan-Supply voltage high (UeHigh)
Automatic
Immediate return fan shutdown
DI1183
AL181
EBM return fan-Line impedance too high (L_high)
Automatic
Immediate return fan shutdown
DI1184
AL182
Warning - Modulating humidifi er maintenance required
Automatic
Display only
DI1185
AL183
Thermal wheel overload
Manual
Immediate thermal wheel shutdown
DI1186
AL184
ZA supply fan - Offl
ine
Automatic
Display only
DI1187
AL185
ZA supply fan - IGBT fault
Automatic
Immediate supply fan shutdown
DI1188
AL186
ZA supply fan - Earth GND fault
Automatic
Immediate supply fan shutdown
DI1189
AL187
ZA supply fan - UZK high
Automatic
Immediate supply fan shutdown
DI1190
AL188
ZA supply fan - UZK low
Automatic
Immediate supply fan shutdown
DI1191
AL189
ZA supply fan - UIN high
Automatic
Immediate supply fan shutdown
DI1192
AL190
ZA supply fan - UIN low
Automatic
Immediate supply fan shutdown
DI1193
AL191
ZA supply fan - Line fault
Automatic
Immediate supply fan shutdown
DI1194
AL192
ZA supply fan - Hall sensor
Automatic
Immediate supply fan shutdown
DI1195
AL193
ZA supply fan - Fire alarm
Automatic
Immediate supply fan shutdown
DI1196
AL194
ZA supply fan - Motor locked
Automatic
Immediate supply fan shutdown
DI1197
AL195
ZA supply fan - Peak current
Automatic
Immediate supply fan shutdown
DI1198
AL196
ZA return fan - Offl
ine
Automatic
Display only
DI1199
AL197
ZA return fan - IGBT fault
Automatic
Immediate return fan shutdown
DI1200
AL198
ZA return fan - Earth GND fault
Automatic
Immediate return fan shutdown
DI1201
AL199
ZA return fan - UZK high
Automatic
Immediate return fan shutdown
DI1202
AL200
ZA return fan - UZK low
Automatic
Immediate return fan shutdown
DI1203
AL201
ZA return fan - UIN high
Automatic
Immediate return fan shutdown
DI1204
AL202
ZA return fan - UIN low
Automatic
Immediate return fan shutdown
DI1205
AL203
ZA return fan - Line fault
Automatic
Immediate return fan shutdown
DI1206
AL204
ZA return fan - Hall sensor
Automatic
Immediate return fan shutdown
DI1207
AL205
ZA return fan - Fire alarm
Automatic
Immediate return fan shutdown
DI1208
AL206
ZA return fan - Motor locked
Automatic
Immediate return fan shutdown
DI1209
AL207
ZA return fan - Peak current
Automatic
Immediate return fan shutdown
DI1210
AL208
IO - Confi guration error
Automatic
Display only
DI1211
AL209
High supply temperature
Automatic
Unit shutdown (in heating mode) /
Display only (in cooling mode)
DI1212
AL210
VDI alarm - Hygiene Inspection
Automatic
Unit shutdown / Display only (parameter)
DI1213
AL211
VDI alarm - Check for contamination, damage and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1214
AL212
VDI alarm - Check for contamination, damage and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1215
AL213
VDI alarm - Functional check of drain and trap
Automatic
Unit shutdown / Display only (parameter)
DI1216
AL214
VDI alarm - Clean wet cooler, mist collector and condensate tray
Automatic
Unit shutdown / Display only (parameter)
DI1217
AL215
VDI alarm - Check for contamination, damage and corrosion on
the air side
Automatic
Unit shutdown / Display only (parameter)
DI1218
AL216
VDI alarm - Check for water precipitation
Automatic
Unit shutdown / Display only (parameter)
DI1219
AL217
VDI alarm - Check empty housings for contamination, damage,
and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1220
AL218
VDI alarm - Check for contamination, damage, microbial growth
and corrosion
Automatic
Unit shutdown / Display only (parameter)
DI1221
AL219
VDI alarm - Check condensate precipitation in the humidifi er
chamber
Automatic
Unit shutdown / Display only (parameter)
DI1222
AL220
VDI alarm - Check steam distribution system for deposits
Automatic
Unit shutdown / Display only (parameter)
DI1223
AL221
VDI alarm - Check spray nozzles for deposits
Automatic
Unit shutdown / Display only (parameter)
DI1224
AL222
VDI alarm - Check drain
Automatic
Unit shutdown / Display only (parameter)
DI1225
AL223
VDI alarm - Determine number of CFU in the humidifi er water
Automatic
Unit shutdown / Display only (parameter)
DI1226
AL224
VDI alarm - Functional check of control valve
Automatic
Unit shutdown / Display only (parameter)
DI1227
AL225
VDI alarm - Check humidity limiter
Automatic
Unit shutdown / Display only (parameter)
DI1228
AL226
VDI alarm - Check for unacceptable contamination, damage
(leakage) and odours
Automatic
Unit shutdown / Display only (parameter)
DI1229
AL227
VDI alarm - Check diff erential pressure
Automatic
Unit shutdown / Display only (parameter)
DI1230
AL228
VDI alarm - Maximum interval until fi rst fi lter stage is to be
changed
Automatic
Unit shutdown / Display only (parameter)
DI1231
AL229
VDI alarm - Maximum interval until second fi lter stage is to be
changed
Automatic
Unit shutdown / Display only (parameter)
DI1232
AL230
VDI alarm - Check accessible duct section for damage
Automatic
Unit shutdown / Display only (parameter)
DI1233
contamination, corrosion, and water precipitation