115
Parameter table
k.air +030220981 rel. 1.2 - 01.12.2020
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
U
N
IT
Ae63
Pre-heat coil step 3 - Working hours
0
0
99
h
R
IR473
PIV3806
Pre-heat coil step 3 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1439
PIV2947
Pre-heat coil step 3 - Working hours left to the maintenance
-
0
99
h
R
IR475
PIV3807
Pre-heat coil step 3 - Working hours reset
-
0
1
-
R/W HR1440
PIV2948
Ae66
Pre-heat coil step 4 - Working hours
0
0
99
h
R
IR477
PIV3808
Pre-heat coil step 4 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1441
PIV2949
Pre-heat coil step 4 - Working hours left to the maintenance
-
0
99
h
R
IR479
PIV3809
Pre-heat coil step 4 - Working hours reset
-
0
1
-
R/W HR1442
PIV2950
Ae69
Re-heat coil pump 1 - Working hours
0
0
99
h
R
IR481
PIV3810
Re-heat coil pump 1 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1443
PIV2951
Re-heat coil pump 1 - Working hours left to the maintenance
-
0
99
h
R
IR483
PIV3811
Re-heat coil pump 1 - Working hours reset
-
0
1
-
R/W HR1444
PIV2952
Ae72
Re-heat coil pump 2 - Working hours
0
0
99
h
R
IR485
PIV3812
Re-heat coil pump 2 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1445
PIV2953
Re-heat coil pump 2 - Working hours left to the maintenance
-
0
99
h
R
IR487
PIV3813
Re-heat coil pump 2 - Working hours reset
-
0
1
-
R/W HR1446
PIV2954
Ae75
Re-heat coil analog output - Working hours
0
0
99
h
R
IR489
PIV3814
Re-heat coil analog output - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1447
PIV2955
Re-heat coil analog output - Working hours left to the maintenance
-
0
99
h
R
IR491
PIV3815
Re-heat coil analog output - Working hours reset
-
0
1
-
R/W HR1448
PIV2956
Ae78
Re-heat coil step 1 - Working hours
0
0
99
h
R
IR493
PIV3816
Re-heat coil step 1 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1449
PIV2957
Re-heat coil step 1 - Working hours left to the maintenance
-
0
99
h
R
IR495
PIV3817
Re-heat coil step 1 - Working hours reset
-
0
1
-
R/W HR1450
PIV2958
Ae81
Re-heat coil step 2 - Working hours
0
0
99
h
R
IR497
PIV3818
Re-heat coil step 2 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1451
PIV2959
Re-heat coil step 2 - Working hours left to the maintenance
-
0
99
h
R
IR499
PIV3819
Re-heat coil step 2 - Working hours reset
-
0
1
-
R/W HR1452
PIV2960
Ae83
Re-heat coil step 3 - Working hours
0
0
99
h
R
IR501
PIV3820
Re-heat coil step 3 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1453
PIV2961
Re-heat coil step 3 - Working hours left to the maintenance
-
0
99
h
R
IR503
PIV3821
Re-heat coil step 3 - Working hours reset
-
0
1
-
R/W HR1454
PIV2962
Ae84
Re-heat coil step 4 - Working hours
0
0
99
h
R
IR505
PIV3822
Re-heat coil step 4 - Working hours threshold (1000hrs)
30
0
99
-
R/W HR1455
PIV2963
Re-heat coil step 4 - Working hours left to the maintenance
-
0
99
h
R
IR507
PIV3823
Re-heat coil step 4 - Working hours reset
-
0
1
-
R/W HR1456
PIV2964
Ae99
Reset total working hours counter of all devices
-
0
1
-
R/W HR1457
PIV2965
Error communication for Import/Export blocks
-
0
9
-
R
IR509
IV3824
Error communication for Import/Export blocks
-
0
9
-
R
IR509
IV3824
Tab. 10.b
10.1.1
B
.
F
ans
R
if
D
escription
D
ev
Min
Max
UoM
D
ir
Modbus
BAC
net
FANS
Ba01
Only for mask usage
TRUE
0
1
-
R
DI701
BV1159
Fan regulation type (0: Static pressure; 1: Air fl ow; 2: Fixed speed)
2
0
2
-
R/W HR1491
PIV2992
Supply fan confi guration error
-
0
1
-
R
DI702
BV1160
Ba03
Enable air quality regulation for fans
FALSE
0
1
-
R/W CS245
BV245
Enable air quality regulation for fresh air OR mixing damper
FALSE
0
1
-
R
CS289
BV289
Air Quality - Fans PID parameters - Proportional gain
1.0
0.0
999.9
-
R/W HR1492
AV2993
Air Quality - Fans PID parameters - Integral time
60
0
999
-
R/W HR1493
PIV2994
Ba06
Air fl ow switch check type: 0=none; 1=common; 2=separated;
0
0
3
-
R/W HR1494
PIV2995
Air fl ow check type
0
0
2
-
R/W HR1495
PIV2996
Number of retry after return or supply air fl ow switch error detected
during start up procedure before turn off the unit
3
0
9
-
R/W HR1496
PIV2997
Timeout for air fl ow switch detection (seconds)
15
1
999
s
R/W HR1497
PIV2998
Air fl ow switch alarm delay time in running mode (s)
3
0
999
s
R/W HR1498
PIV2999
Ba09
Air fl ow check pressure threshold
50.0
0.0
9999.0
Pa
R/W HR1499
AV3000
Ba12
Fan post ventilation time
10
0
600
s
R/W HR1500
PIV3001
Enabling the selection of the temperature regulation for the fans
-
0
1
-
R
DI703
BV1161
Enable fan temperature regulation
FALSE
0
1
-
R/W CS246
BV246
Ba15
Enable fan regulation in case of FreeCooling/FreeHeating
FALSE
0
1
-
R/W CS247
BV247