152
Supervisor variable table
k.air +030220981 rel. 1.2 - 01.12.2020
Variable
D
escription
D
im Modbus
BAC
net
UnitOnOff _Dout.Confi gured_R
Unit status (On/Off ) - Output confi gurated
1
DI438
BV896
CoolHeat_Dout.Val_Hw_R
Cool/Heat status - Hardware value writes from board
1
DI439
BV897
CoolHeat_Dout.Val_W
Cool/Heat status
1
DI440
BV898
CoolHeat_Dout.Enable_W
Cool/Heat status - Enable output
1
DI441
BV899
CoolHeat_Dout.Confi gured_R
Cool/Heat status - Output confi gurated
1
DI442
BV900
GlobalAlrm_Dout.Val_Hw_R
Generic alarm info - Hardware value writes from board
1
DI443
BV901
GlobalAlrm_Dout.Val_W
Generic alarm info
1
DI444
BV902
GlobalAlrm_Dout.Enable_W
Generic alarm info - Enable output
1
DI445
BV903
GlobalAlrm_Dout.Confi gured_R
Generic alarm info - Output confi gurated
1
DI446
BV904
LightAlrm_Dout.Val_Hw_R
Light alarm info - Hardware value writes from board
1
DI447
BV905
LightAlrm_Dout.Val_W
Light alarm info
1
DI448
BV906
LightAlrm_Dout.Enable_W
Light alarm info - Enable output
1
DI449
BV907
LightAlrm_Dout.Confi gured_R
Light alarm info - Output confi gurated
1
DI450
BV908
SrsAlrm_Dout.Val_Hw_R
Serious alarm info - Hardware value writes from board
1
DI451
BV909
SrsAlrm_Dout.Val_W
Serious alarm info
1
DI452
BV910
SrsAlrm_Dout.Enable_W
Serious alarm info - Enable output
1
DI453
BV911
SrsAlrm_Dout.Confi gured_R
Serious alarm info - Output confi gurated
1
DI454
BV912
Humidifi er.Val_Hw_R
Humidifi er - Hardware value writes from board
1
DI455
BV913
Humidifi er.Val_W
Humidifi er
1
DI456
BV914
Humidifi er.Enable_W
Humidifi er - Enable output
1
DI457
BV915
Humidifi er.Confi gured_R
Humidifi er - Output confi gurated
1
DI458
BV916
AuxOut1_Dout.Val_Hw_R
Auxiliary output 1 - Hardware value writes from board
1
DI459
BV917
AuxOut1_Dout.Enable_W
Auxiliary output 1 - Enable output
1
DI461
BV919
AuxOut1_Dout.Confi gured_R
Auxiliary output 1 - Output confi gurated
1
DI462
BV920
AuxOut2_Dout.Val_Hw_R
Auxiliary output 2 - Hardware value writes from board
1
DI463
BV921
AuxOut2_Dout.Enable_W
Auxiliary output 2 - Enable output
1
DI465
BV923
AuxOut2_Dout.Confi gured_R
Auxiliary output 2 - Output confi gurated
1
DI466
BV924
AuxOut3_Dout.Val_Hw_R
Auxiliary output 3 - Hardware value writes from board
1
DI467
BV925
AuxOut3_Dout.Enable_W
Auxiliary output 3 - Enable output
1
DI469
BV927
AuxOut3_Dout.Confi gured_R
Auxiliary output 3 - Output confi gurated
1
DI470
BV928
AuxOut4_Dout.Val_Hw_R
Auxiliary output 4 - Hardware value writes from board
1
DI471
BV929
AuxOut4_Dout.Enable_W
Auxiliary output 4 - Enable output
1
DI473
BV931
AuxOut4_Dout.Confi gured_R
Auxiliary output 4 - Output confi gurated
1
DI474
BV932
MainVlv_Open.Val_Hw_R
Main fl oating valve open - Hardware value writes from board
1
DI475
BV933
MainVlv_Open.Val_W
Main fl oating valve open
1
DI476
BV934
MainVlv_Open.Enable_W
Main fl oating valve open - Enable output
1
DI477
BV935
MainVlv_Open.Confi gured_R
Main fl oating valve open - Output confi gurated
1
DI478
BV936
PreHeatVlv_Open.Val_Hw_R
Pre-heating fl oating valve open - Hardware value writes from
board
1
DI479
BV937
PreHeatVlv_Open.Val_W
Pre-heating fl oating valve open
1
DI480
BV938
PreHeatVlv_Open.Enable_W
Pre-heating fl oating valve open - Enable output
1
DI481
BV939
PreHeatVlv_Open.Confi gured_R
Pre-heating fl oating valve open - Output confi gurated
1
DI482
BV940
ReHeatVlv_Open.Val_Hw_R
Re-Heating fl oating valve open - Hardware value writes from
board
1
DI483
BV941
ReHeatVlv_Open.Val_W
Re-Heating fl oating valve open
1
DI484
BV942
ReHeatVlv_Open.Enable_W
Re-Heating fl oating valve open - Enable output
1
DI485
BV943
ReHeatVlv_Open.Confi gured_R
Re-Heating fl oating valve open - Output confi gurated
1
DI486
BV944
MainVlv_Close.Val_Hw_R
Main fl oating valve close - Hardware value writes from board
1
DI487
BV945
MainVlv_Close.Val_W
Main fl oating valve close
1
DI488
BV946
MainVlv_Close.Enable_W
Main fl oating valve close - Enable output
1
DI489
BV947
MainVlv_Close.Confi gured_R
Main fl oating valve close - Output confi gurated
1
DI490
BV948
PreHeatVlv_Close.Val_Hw_R
Pre-heating fl oating valve close - Hardware value writes from
board
1
DI491
BV949
PreHeatVlv_Close.Val_W
Pre-heating fl oating valve close
1
DI492
BV950
PreHeatVlv_Close.Enable_W
Pre-heating fl oating valve close - Enable output
1
DI493
BV951
PreHeatVlv_Close.Confi gured_R
Pre-heating fl oating valve close - Output confi gurated
1
DI494
BV952
ReHeatVlv_Close.Val_Hw_R
Re-Heating fl oating valve close - Hardware value writes from
board
1
DI495
BV953
ReHeatVlv_Close.Val_W
Re-Heating fl oating valve close
1
DI496
BV954
ReHeatVlv_Close.Enable_W
Re-Heating fl oating valve close - Enable output
1
DI497
BV955
ReHeatVlv_Close.Confi gured_R
Re-Heating fl oating valve close - Output confi gurated
1
DI498
BV956
MainCoil_Step1.Val_Hw_R
Main step 1 - Hardware value writes from board
1
DI499
BV957
MainCoil_Step1.Val_W
Main step 1
1
DI500
BV958
MainCoil_Step1.Enable_W
Main step 1 - Enable output
1
DI501
BV959
MainCoil_Step1.Confi gured_R
Main step 1 - Output confi gurated
1
DI502
BV960
Summary of Contents for k.Air
Page 2: ......
Page 4: ......
Page 6: ......
Page 188: ...188 k air 030220981 rel 1 2 01 12 2020 Note...
Page 189: ...189 k air 030220981 rel 1 2 01 12 2020 Note...
Page 190: ...190 k air 030220981 rel 1 2 01 12 2020 Note...
Page 191: ......