8.2.2 ALARMS AND DIGITAL INPUTS
To set the status of any attached Smoke or Water sensors or digital inputs as the trigger event:
Click on Alarms/Digital Inputs as the Check Condition.
In the Alarms/Digital Inputs Check menu, select the specific Alarm/Digital IO Pin that will trigger the Auto-Response.
Select Trigger on Change to trigger when alarm signal changes, or select to trigger when the alarm signal state changes to either a
Trigger Value of Open (0) or Closed (1).
Check Save Auto-Response.
NOTE: B efore configuring Alarms/Digital Inputs checks in Auto-Response you first must configure the sensor/DIO that is to be
attached to your EMD or LES1200.
8.2.3 UPS AND POWER SUPPLY
To use the properties of any attached UPS as the trigger event:
Select UPS/Power Supply as the Check Condition.
Select the UPS Power Device Property (Input Voltage, Battery Charge %, Load %, Input Frequency Hz or Temperature in °C) to be
checked for the trigger.
Specify the Trigger value that the check measurement must exceed or drop below to trigger the AutoResponse.
Select the Comparison type as being Above Trigger Value or Below Trigger Value to trigger.
Specify any Hysteresis factor to be applied to environmental measurements.
For example, if an Auto-Response is set up with a trigger event of a battery charge below 20% with a Hysteresis of 5 then the trigger
condition will not be set to resolved until the battery charge is above 25%.
FIGURE 8-5. UPS AND POWER SUPPLY SCREEN
CHAPTER 8: ALERTS, AUTO-RESPONSE AND LOGGING