Learning Basic Features
Acc/Dec Pattern Configuration
A Linear Accel and Decel pattern features a linear increase (and decrease) of the output frequency
at a fixed rate. An S-curve pattern provides a smoother and more gradual increase (and/or
decrease) of output frequency. Acc/Dec gradient level patterns can be configured to enhance and
smooth the inverter’s acceleration and de
celeration curves. This is ideal for lift-type loads or
elevators. An S-curve can be set with Ad.01 (accel) and Ad.02 (decel) and gradient levels can be
adjusted using Ad.03 ~ Ad.06.
Group Code
Name
Setting
Setting Range
Unit
bA
08
Acc/Dec reference
frequency
0 Max Freq
0
–
1
-
Ad
01
Acceleration pattern 0 Linear
0
–
1
-
02
Deceleration pattern 1 S-curve
-
03
S-curve acceleration
start point gradient
40
1
–
100
%
04
S-curve acceleration
end point gradient
40
1
–
100
%
05
S-curve deceleration
start point gradient
40
1
–
100
%
06
S-curve deceleration
end point gradient
40
1
–
100
%
Acc/Dec Pattern Setting Details
Code and Features
Description
Ad.01
Acceleration Pattern
Select 0 (Linear) or 1 (S-Curve) Acceleration Pattern
Ad.02
Deceleration Pattern
Select 0 (Linear) or 1 (S-Curve) Deceleration Pattern
Ad.03
Acc S Start
Ad.03 sets the gradient level at the start of the acceleration curve. The
set percentage applies to 50% below the first half of the total
acceleration curve. When the frequency reference is set at 60 Hz and
Ad.03 is set to 50%, S-Curve acceleration will be applied to 0
–
15 Hz.
(50% below half the reference frequency). Linear acceleration will be
applied to the 15-30 Hz. section.
Ad.04
Acc S End
Ad.04 sets the gradient level at the end of the acceleration curve. The
set percentage applies to the second half of the total acceleration curve
where operating frequency is reaching the reference frequency. When
the reference frequency is 60 Hz. and Ad.04 is set to 50%, S-Curve
acceleration will be applied to 45-60 Hz. (50% above half the reference
frequency). Linear acceleration will be applied to the 30
–
45 Hz. section.
Ad.05
Dec S Start
–
Sets the gradient level at the start of S-curve deceleration. S-Curve
deceleration is applied to the portion of the deceleration curve that is
50% above half the reference frequency (60-45 Hz.). Same as S-Curve
End acceleration.
Ad.06
Dec S End
Sets the gradient level at the end of S-curve deceleration. S-Curve
deceleration is applied to the portion of the deceleration curve that is
50% below half the reference frequency (15-0 Hz.). Same as S-Curve
start acceleration.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...