Example: Set Pr.15 (Al Lost Level) to 1 (Below x 1), Pr.12 (Lost Cmd Mode) to 2 (Dec), and
Pr.13 (Lost Cmd Time) to 5 sec. Then it operates as follows:
Note
If speed reference is lost while using communication options or the integrated RS-485
communication, the protection function operates regardless of Pr.12 setting. Operates
after the command loss decision time set at Pr.13 (Lost Cmd Time) has passed.
When using analog signals, when signal returns above the level set in Pr.15, the inverter
clears the fault and returns to normal operation.