219
Table of Functions
890054-00-00
GM2 Series VFD
Input Terminal Block Function Group
(PAR→In
)
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F SL
Ref.
In.00
-
Jump Code
1
–99
65
O
O
O
In.01
0h1501
Frequency
for
maximum
analog input
Start frequency
–
Maximum
frequency(Hz)
Maximum
frequency
O
O
O
In.02
0h1502
Torque at
maximum
analog input
0.0
–200.0 (%)
100
O
X
X
In.05
0h1505
V1 input
voltage
display
-12.00
–12.00 (V)
0
-
O
O
In.06
0h1506
V1 input
polarity
selection
0
Unipolar
0:Unipolar
X
O
O
1
Bipolar
In.07
0h1507
Time
constant of
V1 input
filter
0
–10000 (ms)
100
O
O
O
In.08
0h1508
V1 Minimum
input voltage
0.00
–10.00 (V)
0
O
O
O
In.09
0h1509
V1 output at
Minimum
voltage (%)
0.00
–100.00 (%)
0
O
O
O
In.10
0h150A
V1
Maximum
input voltage
0.00
–12.00 (V)
10
O
O
O
In.11
0h150B
V1 output at
Maximum
voltage (%)
0.00
–100.00 (%)
100
O
O
O
In.12
1
0h150C
V1 Minimum
input voltage
-10.00
–0.00 (V)
0
O
O
O
In.13
1
0h150D
V1 output at
Minimum
voltage (%)
-100.00
–0.00 (%)
0
O
O
O
In.14
1
0h150E
V1
Maximum
input voltage
-12.00
–0.00 (V)
-10
O
O
O
In.15
1
0h150F
V1 output at
Maximum
voltage (%)
-100.00
–0.00 (%)
-100
O
O
O
In.16
0h1510
Changing
rotation
direction of
V1
0
No
0: No
O
O
O
1
Yes
In.17
0h1511
V1
quantization
level
0.00
2
, 0.04
–10.00
(%)
0.04
X
O
O
In.35
0h1523
V0 input
voltage
display
0.00
–5.00 (V)
0
-
O
O
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...