Technical Specification
890054-00-00
266
GM2 Series VFD
Heat Emission
The following table provides data on the heat generated by the inverters. Heat emissions are based
on operation at room temperature and the carrier frequency set at default.
Inverter Capacity
Efficiency
(%)
Total
Losses
(W)
Internal
Losses
(W)
External
Losses
(W)
Normal Duty
Heavy Duty
kW
HP
Amps
kW
HP
Amps
3-phase
240V
0.75 1
3.1
0.4
0.5
2.5
96.40
22
17
6
1.5
2
6
0.75
1
5
96.40
45
17
28
2.2
3
9.6
1.5
2
8
96.70
79
17
62
4
5
12
2.2
3
11
96.70
117
17
99
5.5
7.5
18
4
5
17
96.80
208
18
190
7.5
10
30
5.5
7.5
24
96.90
281
19
262
11
15
40
7.5
10
32
96.90
382
19
364
3-phase
480V
0.75 1
2
0.4
0.5
1.3
96.00
24
17
7
1.5
2
3.1
0.75
1
2.5
96.80
42
17
24
2.2
3
5.1
1.5
2
4
97.30
71
18
53
4
5
6.9
2.2
3
5.5
97.50
99
18
81
5.5
7.5
10
4
5
9
97.60
176
19
157
7.5
10
16
5.5
7.5
12
97.80
231
20
211
11
15
23
7.5
10
16
97.80
315
20
295
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...