Table of Functions
214
GM2 Series VFD
890054-00-00
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
selection
1
DI
Dependent
Ad.71
9
0h1347
Safe
operation stop
options
0
Free-Run
0: Free-
Run
X
O
O
1
Q-Stop
2
Q-Stop
Resume
Ad.72
9
0h1348
Safe
operation
deceleration
time
0.0
–600.0 (s)
5
O
O
O
Ad.74
0h134A
Selection of
regeneration
avoidance
0
No
0: No
X
O
O
1
Yes
Ad.75
0h134B
Voltage level
of
regeneration
avoidance
200 V: 300
–400 V
350
X
O
O
400 V: 600
–800 V
700
Ad.76
10
0h134C
Compensation
frequency limit
of
regeneration
avoidance
0.00
–10.00 Hz
1
X
O
O
Ad.77
10
0h134D
Regeneration
avoidance P
gain
0.0
–100.0%
50
O
O
O
Ad.78
10
0h134E
Regeneration
avoidance I
gain
20
–30000 (ms)
500
O
O
O
Ad.79
0h134F
DB Unit turn
on voltage
level
200 V: Min
11
–
400[V]
390[V]
X
O
O
-
400 V: Min
11
–
800[V]
780[V]
Ad.80
0h1350
Fire Mode
selection
0
None
0: None
X
O
O
1
Fire Mode
2
Fire Mode
Test
Ad.81
12
0h1351
Fire Mode
Start frequency
–
Maximum
frequency [Hz]
60
X
O
O
Operating
frequency
Ad.82
12
0h1352
Fire Mode
0
Forward
0:
Forward
X
O
O
Run direction
1
Reverse
Ad.83
12
Fire Mode
operation
count
Not configurable
-
-
-
-
[1] Displayed when Ad. 01 is set to 1 (S-curve).
[2] Displayed when the Ad. 02 code is set to 1 (S-curve).
[3] Displayed when Ad. 07 is set to 1 (DC-Start).
[4] Displayed when Ad. 08 is set to 1 (DC-Brake).
[5] Displayed when the Ad.24 code is set to 1 (Yes).
[6] Displayed when the Ad.27 code is set to 1 (Yes).
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...